Huawei ESS-240V12-9AhBPVBA04 Quick Manual page 51

Hide thumbs Also See for ESS-240V12-9AhBPVBA04:
Table of Contents

Advertisement

ESS-240V12-(9AhBPVBA04, 7AhBPVBA04) Battery
Pack
Quick Guide
Check
Content
Battery
string
charge
voltage
Battery
temperatu
re sensor
measure
ment
accuracy
Battery
managem
ent
parameter
settings
Issue 02 (2022-06-30)
Baseline
Requirement
● Equalized
charge
voltage: 14.1
V x Number
of batteries
(tolerance
±1%)
● Float charge
voltage: 13.5
V x Number
of batteries
(tolerance
±1%)
The deviation
between the
detected
temperature
and the
displayed
temperature
must be less
than 3°C.
Check that the
settings of
battery
management
parameters
meet the
requirements in
the user
manual.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Troubleshooting
1. If the voltage drop
between the battery
string output
terminals and the
battery input
terminals at the
UPS side is greater
than 1% of the
battery string
voltage, check
whether the cable
between the battery
string and the UPS
is excessively long,
or the cable
diameter is
excessively small.
2. Check whether the
equalized charge
voltage and float
charge voltage are
correctly set for the
UPS.
3. If the fault persists,
contact the
technical support
personnel.
1. Install the battery
temperature sensor
in the correct
position.
2. Replace the battery
temperature sensor.
Set parameters
correctly.
4 Installation
Maintenance Interval
Monthly
Quarterly
Quarterly
45

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ess-240v12-7ahbpvba04

Table of Contents