Recharge Method Of The Ups2000-H-6 Kva/10 Kva; Battery Pack Recharge Control Parameters - Huawei ESS-240V12-9AhBPVBA04 Quick Manual

Hide thumbs Also See for ESS-240V12-9AhBPVBA04:
Table of Contents

Advertisement

ESS-240V12-(9AhBPVBA04, 7AhBPVBA04) Battery
Pack
Quick Guide
Step 3 After the battery pack is recharged, shut down the UPS. Remove the battery cables
from the battery pack and then from the UPS.
----End

3.4 Recharge Method of the UPS2000-H-6 kVA/10 kVA

3.4.1 Battery Pack Recharge Control Parameters

The following describes how to use the UPS2000-H-10 kVA to recharge a battery
pack.
1.
Issue 02 (2022-06-30)
Set charge parameters for the UPS based on the number of battery packs
connected in parallel.
Device
UPS2000-H-10 kVA
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Transportation and Storage Requirements
Charge Voltage (V)
288±5
Charge curr. limit coef.
(C)
0–0.15
15