Troubleshooting
Fault
Fault indication
code
Internal Fault
79
LHMI module
Internal Fault
79
LHMI module
Internal Fault
80
RAM error
Internal Fault
81
ROM error
Internal Fault
82
EEPROM error
Internal Fault
82
EEPROM error
Internal Fault
83
FPGA error
Internal Fault
84
RTC error
Table continues on the next page
94
Fast self-
Additional
recovery
information
attempt
code 10: Watchdog
reset
Start up error: EE-
No
PROM error in LHMI
module. The fault
indication may not
be seen on the
LHMI during the
fault.
Runtime error:
Yes
LHMI LCD error.
The fault indication
may not be seen
on the LHMI during
the fault.
Runtime error: Er-
No
ror in the RAM
memory on the
CPU module.
Runtime error: Er-
Yes
ror in the ROM
memory on the
CPU module.
Start up error: Er-
No
ror in the EEPROM
memory on the
CPU module.
Start up error: CRC
Yes
check failure in the
EEPROM memory
on boot-up on the
CPU module.
Runtime error: Er-
Yes
ror in the FPGA on
the CPU module.
Start up error: Er-
Yes
ror in the RTC on
the CPU module.
Slow 10min
self-
recovery
Immediate
(# of
attempts)
IRF-mode
No
Yes
Yes (3)
No
Yes (3)
No
No
Yes
No
Yes
Yes (3)
No
Yes (3)
No
No
Yes
1MRS759118 D
Action in permanent fault
state
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restarting,
check LHMI connection ca-
ble and connection to be
proberly fixed. If then not
recovered by restarting, ex-
change the LHMI module.
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restarting,
check LHMI connection ca-
ble and connection to be
proberly fixed. If then not
recovered by restarting, ex-
change the LHMI module.
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
ing, replace the relay, most
probably hardware failure
in CPU module.
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
ing, replace the relay, most
probably hardware failure
in CPU module.
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
ing, replace the relay, most
probably hardware failure
in CPU module.
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
ing, replace the relay, most
probably hardware failure
in CPU module.
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
ing, replace the relay, most
probably hardware failure
in CPU module.
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
ing, replace the relay, most
probably hardware failure
in CPU module.
REX640
Operation Manual