Rectifying Common Faults; Ac Failure - Huawei Telecom Power TP48200A-HX09A3 User Manual

Table of Contents

Advertisement

TP48200A-HX09A3, TP48200A-HX09A4,
TBC300A-DCA3, TBC300A-DCA5 and
TBC300A-TCA2 Telecom Power
User Manual
Maintenance
Item
board
TEC04C
Electrical
specifications
Preventive
maintenance
inspection (PMI)
Appearance
Grounding

4.2 Rectifying Common Faults

4.2.1 AC Failure

Possible Causes
Measures
1.
2.
Issue 04 (2019-11-15)
Check Whether
Check Method
board works
checking the
normally.
indicator and
alarms
The TEC04C works
By observing, and
normally.
checking the fan
and the
temperature.
The output voltage
Multimeter
is normal.
Indicators are
By observing
normal.
The paint or
By observing
electroplated
coating on the
cabinet flakes off or
has scratches.
The ground point
By observing the
properly connects
grounding and
to the ground bar in
using a screwdriver
the equipment
or wrench.
room.
The AC input power cable is faulty.
The AC input circuit breaker is OFF.
The power grid is faulty.
Check whether the AC input cable is loose. If so, secure the AC input cable.
Check whether the AC input circuit breaker is OFF. If so, handle the fault which caused
the AC input circuit breaker to turn OFF and then switch on the circuit breaker.
Copyright © Huawei Technologies Co., Ltd.
Repair When
Measures
board works
control board.
abnormally.
The TEC module is
Replace the
damaged and
TEC04C.
cannot effectively
cool the air.
The battery circuit
For details, see 4.2
voltage or load
Rectifying
circuit voltage
Common Faults.
exceeds its
threshold.
An alarm is
generated.
The surface is
Repaint or repair
damaged or
the shell.
distorted.
The cable
Secure the ground
connecting the
point or replace the
ground point and
cable.
the ground bar in
the equipment room
is loose or
damaged.
4 Maintenance