C Associations Between Alarms And Dry Contacts On The Uim - Huawei Telecom Power TP48200A-HX09A3 User Manual

Table of Contents

Advertisement

TP48200A-HX09A3, TP48200A-HX09A4,
TBC300A-DCA3, TBC300A-DCA5 and
TBC300A-TCA2 Telecom Power
User Manual
C
Associations Between Alarms and Dry
Table C-1 Associations between alarms and dry contacts
Dry Contact
Dry contact input
Dry contact output
The default mode (Close:
alarm; Open: normal) can
be changed.
Issue 04 (2019-11-15)
Silk Screen
Associated Alarm
DIN1
Dry contact input 1
DIN2
Dry contact input 2
DIN3
Dry contact input 3
DIN4
Dry contact input 4
DIN5
Dry contact input 5
DIN6
Dry contact input 6
ALM1
AC Failure/Long Mains Failure
ALM2
DC Ultra Overvoltage/DC Overvoltage/DC Ultra
Undervoltage/DC Undervoltage
ALM3
Rectifier Fault/Rectifier Protection/Rectifier
Communication Failure/Rectifier Fault
(Redundant)/Rectifier Fault
(Non-redundant)/Multi-Rectifier Fault/All Rectifiers Fail to
Communicate
ALM4
AC SPD Fault/DC SPD Fault
ALM5
Load Fuse Break/Battery Fuse Break
ALM6
Battery High Temperature/Battery Low
Temperature/Battery Very High Temperature/Battery Very
Low Temperature
ALM7
Door Alarm (for the power cabinet and battery cabinets)
ALM8
For the power cabinet: Indoor Vent High Temperature/Fan
1/2/3/4 Fault
For the battery cabinet: Internal Circular Fan Fault/External
Copyright © Huawei Technologies Co., Ltd.
C Associations Between Alarms and Dry Contacts on the
Contacts on the UIM
UIM
97