Huawei Telecom Power TP48200A-HX09A3 User Manual page 27

Table of Contents

Advertisement

TP48200A-HX09A3, TP48200A-HX09A4,
TBC300A-DCA3, TBC300A-DCA5 and
TBC300A-TCA2 Telecom Power
User Manual
Item
User interface module (UIM)
Sensor
Lamp
Maximum output power
Table 2-2 TBC300A-DCA3, TBC300A-DCA5, and TBC300A-TCA2 configurations
Item
Application
environment
Heater
Temperature control
unit (TCU)
Sensor
Battery
Issue 04 (2019-11-15)
TP48200A-HX09A3 and TP48200A-HX09A4
UIM02C
Mandatory: one door status sensor and one ambient temperature sensor
Optional: one smoke sensor, one ambient temperature and humidity sensor,
and one water sensor
Optional: one lamp
12 kW
TBC300A-DCA3
Class B
None
Battery compartment:
direct ventilation and
TCUA control box
One door status sensor and one battery temperature sensor
Battery compartment of two layers: two front-access battery strings (12 V/100 Ah)
can be configured.
Class B environments refer to indoor environments in which the ambient temperature and humidity
are not controlled and outdoor environments (with simple shielding measures) where humidity can
reach 100%.
Class C environments refer to sea environments or outdoor land environments (with simple
shielding measures) near pollution sources. If a site is near a pollution source, it is at most 3.7 km
away from salt water, such as the sea and salt lakes, 3 km away from heavy pollution sources, such
as smelteries, coal mines, and thermal power plants, 2 km away from medium pollution sources,
such as chemical, rubber, and galvanization industries, and 1 km away from light pollution sources,
such as packing houses, tanneries, and boiler rooms.
Copyright © Huawei Technologies Co., Ltd.
TBC300A-DCA5
Class B
Enabled
Battery compartment:
direct ventilation and
TCUA control box
2 Overview
TBC300A-TCA2
Class C
TEC with a heating
function
Battery compartment:
TEC and TCUA control
box
20

Advertisement

Table of Contents