THERMAL DISINFECTION PROCEDURE PAGE 17 COMMISSIONING PAGE 19 SERVICE AND MAINTENANCE PAGE 21 SPARE PARTS PAGE 27 SENSOR PROGRAM PAGE 28 COMMISSIONING AND / OR MAINTENANCE REPORT PAGE 31 TROUBLESHOOTING PAGE 33 PRODUCT WARRANTY PAGE 36 Call 1300 369 273 www.enware.com.au...
Page 3
IN WALL ADJUSTMENT 73.3 73.3 TRIM DOWN TO SUIT AFTER INSTALLATION NOTE: Enware Australia advises: 1. Due to ongoing Research and Development, specifications may change without notice. 2. Component specifications may change on some export models www.enware.com.au Call 1300 369 273...
FRONT OF with battery with mains WALL operated operated component FRONT OF WALL FRONT OF WALL Sensors will not operate if components are not paired correctly MAINS MAINS POWER ATM621 12V Mains Power In-Wall Component MAINS www.enware.com.au Call 1300 369 273...
P R E S S U R E L O S S F L O W R A T E * In accordance with AS/NZS3500. Enware products are to be installed in accordance with the Plumbing Code of Australia (PCA) and AS/NZS3500.
INSTALLATION COMPLIANCE INSTALLATION The Enware Aquablend Thermostatic Mixers should be ® installed using the appropriate Standard, Code of Practice Note to Installers: and legislation applicable to each state and following the The Auto Flush function must only be activated details outlined in this section.
Health Facility Guidelines). STEP 2 If installing within a frame wall, fit mounting timber in the desired location for box support. Enware recommend 13mm ply wood fixed between two vertical in wall studs. NOTE: plywood needs to cover the entire back section of the box, so the valve body can be fixed.
Page 9
If the cable is not long enough, use an extended transformer (ENMS230 - available from Enware). Use a conduit to run the transformer cable between the power point and the box, to allow for easy component replacement in future.
Check that no part of the box protrudes past the finished wall, and deburr trimmed edges. STEP 2 Fit the chrome back support bracket and secure with four screws supplied. SEE IMAGE 9 IMAGE 8 IMAGE 9 Call 1300 369 273 www.enware.com.au...
Page 11
3/8” Allen key, making sure it finishes hard up against the spout IMAGE 10: SHOWING SPOUT SUPPORT NUT support nut. SEE IMAGE 13 IMAGE 11 IMAGE 12 IMAGE 13 www.enware.com.au Call 1300 369 273...
Page 12
FITTING THE FACE PLATE STEP 9 Remove the spout from spout retainer. STEP 10 Connect the sensor cable marked with Bluetooth label to the battery or transformer. 100mm BLUETOOTH® CABLE LABEL MAINS BATTERY SENSOR SOLENOID IMAGE 18 Call 1300 369 273 www.enware.com.au...
Page 13
2x voids in the base of the face plate bracket until it sits flush. Secure in place using the 2x M4 Allen head screws and tighten with an Allen key. SEE IMAGE 20 and 21 IMAGE 19 IMAGE 20 IMAGE 21 www.enware.com.au Call 1300 369 273...
Page 14
SEE IMAGE 25 IMAGE 23 (Refer to Page 19 Setting the Outlet Temperature, Steps 3 & 4). STEP 17 When complete, fit the chrome temperature adjuster cover onto the face plate. IMAGE 24 IMAGE 25 Call 1300 369 273 www.enware.com.au...
∙ Afterflow time, maximum flow time, sensor range, and sensor sensitivity can be adjusted, and Auto Flush function can be activated. See Sensor Program on page 28. *After installation this sheet may be affixed adjacent to the tap for user instruction. www.enware.com.au Call 1300 369 273...
Page 16
Place hand in front of sensor at Move hand in towards sensor and 10cm for 1 sec pulling up Hand too close to sensor Wave quickly in front of sensor (does not activate) (does not activate) Call 1300 369 273 www.enware.com.au...
THERMAL DISINFECTION PROCEDURE PROCEDURE FOR FLUSHING WITH HOT WATER FOR DISINFECTION Enware Product Code: ATMS698 - eSQX™ Bypass Adaptor Kit The internal components can be flushed with full hot water temperature by adding a bypass to strainer / check valve assembly ports, using the following procedure.
Page 18
IMAGE 58 STEP 15 Take spout off. Then fit front plate and install spout back on. STEP 16 Commission the valve and set the valve to required temperature, according to the Commissioning Procedure on page 19. Call 1300 369 273 www.enware.com.au...
(maximum) temperature is achieved. SEE IMAGE 27 STEP 4 Once this desired temperature is set, make sure it stays steady for a minimum of 60 seconds. Remove the Allen key without changing the temperature gear position. IMAGE 27 www.enware.com.au Call 1300 369 273...
Page 20
Ensure that all details of the Commissioning Report are completed and signed by the relevant signatories and a copy is kept with the installer and owner of the premises. The valve is now commissioned and it can be used within the technical limits of operation. Call 1300 369 273 www.enware.com.au...
The valve should be serviced annually, unless the installation conditions dictate more frequent servicing. ANNUAL MAINTENANCE PROCEDURE Every 12 months the Enware Aquablend eSQX™ Thermostatic Mixer must be inspected and ®...
Page 22
SERVICE AND MAINTENANCE SERVICING THE STRAINERS AND CHECK VALVES Enware Product Code: ATMS693 - SQX™ Strainer / Check Valve Assembly (1 Pair) Prior to servicing the strainers, turn off both the hot and cold water supply via the isolation valve within the inlet connectors. SEE IMAGE 26 on page STEP 1 Using a 3/8”...
Page 23
SERVICING THE THERMOSTATIC CARTRIDGE Enware Product Code: ATMS600 - Aquablend SQX™ Thermostatic Cartridge ® ATMS699 - eSQX™ Temperature Control Gear Ensure the water supplies to both the hot and cold inlets are isolated prior to commencing. SEE IMAGE 31 STEP 1...
Page 24
SERVICE AND MAINTENANCE SERVICING THE SOLENOID VALVE Enware Product Code: ATMS625 - Solenoid Prior to servicing, turn off both the hot and cold water supply via the Isolation valve within the inlet connectors. SEE IMAGE 26 on page 19. Ensure faceplate bracket is removed and the solenoid valve is disconnected from the sensor.
Page 25
CHANGING THE BATTERY For battery operated models only. Enware Product Code: ENMS204 - 6V Lithium 2CR5 Battery ENMS206 - 6V Lithium 2CR5 Battery with casing If the mixer fails to function, and there is a RED light displayed within the sensor when trying to activate the product, this means that the battery is low in voltage and needs to be replaced.
Page 26
- see Step 1 (A-D) Annual Maintenance Procedure on page 21. Use an M6 Allen key to unscrew the access cover off, then fit a Pete’s Plug (Enware part - ATMS1221) to the 1/4” thread port. Measurement probe from thermometer or pressure gauge can be inserted into the Pete’s Plug to take measurements.
Spout grub screw - M5 Dog point 672453 Face plate fixing screw (each) (socket HD cap SS304 M4 x 10 CSK) 671484 Pete's Plug 1/4" Test Point Adaptor ATMS1221 ATMS698 eSQX Bypass Adaptor Kit for Thermal Disinfection www.enware.com.au Call 1300 369 273...
Apple, the Apple logo, iPhone, iPad, and iPod touch are trademarks of Apple Inc., registered in the U.S. and other countries. App Store is a service mark of Apple Inc. Google Play and the Google Play logo are trademarks of Google Inc. Call 1300 369 273 www.enware.com.au...
Page 29
HOW TO CHANGE THE SENSOR PROGRAM SETTINGS 1. To access the sensor function program, press the settings button 2. Enter the password. (Contact Enware for default password, or your selected password if already registered). 3. Change the settings as desired.
Page 30
Enter the name of your choice to identify the location of the tap. Password: Set the password of your choice to limit access to the settings by others (e.g. for public places). Default password for factory setting is "Electra". Call 1300 369 273 www.enware.com.au...
2. The valve manufacturer / 3. The Australian Standards authority supplier requirements for Plumbing and Drainage YES NO YES NO YES NO If NO, give details and action taken: www.enware.com.au Call 1300 369 273...
Page 32
Contractor Name (print) Signature Licensed Plumber Contractors Phone No Date Owner / Occupier Signature Date NOTE: A duplicate copy of this report is to be retained at the site for any inspection by authorised persons Call 1300 369 273 www.enware.com.au...
Clean strainers ensuring debris is removed Water is leaking Mixer body o-rings are worn or Replace sealing o-rings from mixer body damaged Fitting connections have loosened Tighten all connections and threads, ensure they are sealed www.enware.com.au Call 1300 369 273...
Page 34
Thermostatic cartridge contains Clean the cartridge ensuring that all debris is temperature doesn’t debris, has failed or is damaged removed and components are not damaged. change when the Replace if necessary temperature cam is rotated Call 1300 369 273 www.enware.com.au...
Page 35
/ sensor / battery / instructions and replace if needed power supply Power supply is turned off Turn on power supply Sensor is constantly activated by Remove interfering object an object in front of sensor www.enware.com.au Call 1300 369 273...
3 Years warranty, parts supply only is applicable to the thermostatic cartridge component assembly. If the valve is sold by a party other than ENWARE then it is sold by that seller as principal and the seller has no authority from ENWARE to give any additional warranty on behalf of ENWARE.