enware AQUABLEND ESQX TOUCH FREE SERIES Installation & Maintenance Instructions Manual

Thermostatic mixers active sense system / wave on - wave off system

Advertisement

AQUABLEND ESQX TOUCH FREE
THERMOSTATIC MIXERS
Installation & Maintenance Instructions
ACTIVE SENSE SYSTEM
WAVE ON - WAVE OFF SYSTEM
I00057_JUN18
Call 1300 369 273
www.enware.com.au
Enware Australia Pty Limited
9 Endeavour Rd Caringbah NSW 2229 Australia
Ph: +61 2 8556 4000 Fax: +61 2 8556 4055

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AQUABLEND ESQX TOUCH FREE SERIES and is the answer not in the manual?

Questions and answers

Summary of Contents for enware AQUABLEND ESQX TOUCH FREE SERIES

  • Page 1 Installation & Maintenance Instructions ACTIVE SENSE SYSTEM WAVE ON - WAVE OFF SYSTEM I00057_JUN18 Call 1300 369 273 www.enware.com.au Enware Australia Pty Limited 9 Endeavour Rd Caringbah NSW 2229 Australia Ph: +61 2 8556 4000 Fax: +61 2 8556 4055...
  • Page 2: Table Of Contents

    SERVICE AND MAINTENANCE PAGE 18 CHANGING THE SENSOR PROGRAM PAGE 27 PROGRAM - ACTIVE SENSOR PAGE 28 PROGRAM - WAVE ON/OFF PAGE 29 TROUBLESHOOTING PAGE 30 PRODUCT WARRANTY PAGE 33 COMMISSIONING AND/OR MAINTENANCE REPORT PAGE 34 Call 1300 369 273 www.enware.com.au...
  • Page 3 IN WALL ADJUSTMENT 73.3 73.3 TRIM DOWN TO SUIT AFTER INSTALLATION NOTE: Enware Australia advises: 1. Due to ongoing Research and Development, specifications may change without notice. 2. Component specifications may change on some export models www.enware.com.au Call 1300 369 273...
  • Page 4: Product Components Front Of Wall

    ACTIVE SENSE Sensor below outlet Active Sense Front of Wall Component Only with 230mm Fixed Spout with Laminar Flow - Mains Powered ATAM C2L3 - 8Lpm ATAM C2L5 - 6Lpm MAINS ATAM C2L6 - 4.5Lpm Call 1300 369 273 www.enware.com.au...
  • Page 5: Product Components In-Wall

    ATWM C1L3 - 8 Lpm ATWM C1L5 - 6 Lpm ATM621 ATWM C1L6 - 4.5 Lpm 12V Mains In-Wall MAINS ACTIVE SENSE Component ATAM C1L3 - 8 Lpm ATAM C1L5 - 6 Lpm ATAM C1L6 - 4.5 Lpm www.enware.com.au Call 1300 369 273...
  • Page 6: Technical Information

    P R E S S U R E L O S S F L O W R A T E In accordance with AS/NZS3500. Enware products are to be installed in accordance with the Plumbing Code of Australia (PCA) and AS/NZS3500. Installations not complying with PCA and AS/NZS 3500 may void the product and performance warranty provisions.
  • Page 7: Installation Compliance

    INSTALLATION The ENWARE AQUABLEND Thermostatic Mixers should be installed using the appropriate Standard, Code of Practice and legislation applicable to each state and following the details outlined in this section. They must be installed by a licensed plumber, or where applicable, a licensed plumber who has undertaken accredited training in Thermostatic Mixing Valves.
  • Page 8: In-Wall Installation Procedure

    AUSHFG (Australasian Health Facility Guidelines) STEP 2 If installing within a frame wall, fit mounting timber in the desired location for box support. Enware recommend 13mm ply wood fixed between two vertical in wall studs. Note: plywood needs to cover the entire back section of the box, so the valve body can be fixed (see STEP 6).
  • Page 9 If the cable is not long enough, use an extended transformer (ENMS230 - available from Enware). Use a conduit to run the transformer cable between the power point and the box, to allow for easy component replacement in future.
  • Page 10: Front Of Wall Installation Procedure

    Check that no part of the box protrudes past the finished wall, and deburr trimmed edges. IMAGE 8 STEP 2 Fit the chrome back support bracket and secure with four screws supplied. SEE IMAGE 10 IMAGE 9 Call 1300 369 273 www.enware.com.au...
  • Page 11 STEP 5 Apply thread sealant or tape to outlet thread and screw on the spout retainer using 3/8” Allen key, making sure it finishes hard up against the spout support nut. SEE IMAGE 13 IMAGE 13 www.enware.com.au Call 1300 369 273...
  • Page 12 Note: Do not high pressure test the supply system, as this may damage the thermostatic cartridge (Max 1000KPa). STEP 8 Use the 3/8” Allen key and wind the temperature adjustment gear anti clockwise until it comes to a firm stop. This will close the thermostatic valve. IMAGE 16 SEE IMAGE 16 Call 1300 369 273 www.enware.com.au...
  • Page 13 2x lower tabs into the 2x voids in the base of the face plate bracket until it sits flush. Secure in place using the 2x M4 Allen head screws and tighten with an Allen key. SEE IMAGE 20 and 21 IMAGE 19 IMAGE 20 IMAGE 21 www.enware.com.au Call 1300 369 273...
  • Page 14 SEE IMAGE 25 (Refer to Page 16 Setting the Outlet Temperature, Steps 3 & 4) STEP 17 When complete, fit the chrome temperature adjuster cover onto the plate. IMAGE 25 Call 1300 369 273 www.enware.com.au...
  • Page 15: Operating Instructions

    OFF after a set period. (Factory default setting is 15 sec, range 8 sec - 180 sec) If Optional 15 sec Lockout Time Function is set: After turning OFF the tap cannot be turned ON again for 15 seconds. www.enware.com.au Call 1300 369 273...
  • Page 16: Commissioning And In Service Testing

    (maximum) temperature is achieved. SEE IMAGE 27 STEP 4 Once this desired temperature is set, make sure it stays steady for a minimum of 60 seconds. Remove the Allen key without changing the temperature gear position. IMAGE 27 Call 1300 369 273 www.enware.com.au...
  • Page 17 Ensure that all details of the Commissioning Report are completed & signed by the relevant signatories & a copy is kept with the installer and owner of the premises. The valve is now commissioned and it can be used within the technical limits of operation. IN SERVICE TESTING Enware Australia recommends that Thermostatic Mixing Valves have monthly temperature checks and adjustments as needed during the life of the valves. The results should be recorded for future reference. The purpose of the in-service test is to regularly monitor and record the performance of the thermostatic taps.
  • Page 18: Service And Maintenance

    ANNUAL MAINTENANCE PROCEDURE Every 12 months the ENWARE AQUABLEND SQX thermostatic Mixer should be inspected & tested. The valve & surrounding area should be inspected for leaks or water damage and appropriate action taken if required.
  • Page 19 SERVICING THE STRAINERS AND CHECK VALVES Enware Product Code: ATMS693 - Strainer / Check Valve Assembly (1 Pair) Prior to servicing the strainers, turn off both the hot and cold water supply via the Isolation valve within the inlet connectors. SEE IMAGE 27.
  • Page 20 SERVICE AND MAINTENANCE SERVICING THE THERMOSTATIC CARTRIDGE Enware Product Code: ATMS600 - Aquablend SQX Thermostatic Cartridge Ensure the water supplies to both the hot and cold inlets are isolated prior to commencing. CARTRIDGE HEX NUT SEE IMAGE 31 STEP 1 Remove the faceplate bracket by...
  • Page 21 SERVICING THE SOLENOID VALVE Enware Product Code: ATMS625 - Solenoid Prior to servicing, turn off both the hot and cold water supply via the Isolation valve within the inlet connectors SEE IMAGE 27 Ensure face plate bracket is removed and the solenoid valve is disconnected from the sensor.
  • Page 22 SERVICE AND MAINTENANCE CHANGING THE BATTERY Enware Product Code: ENMS204 - 6V Lithium 2CR5 Battery ENMS205 - 6V Lithium 2CR5 Battery with casing If the mixer fails to function and there is a RED light displayed within the sensor when trying to activate the product, this means that the battery is low in voltage and needs to be replaced.
  • Page 23 Using an M6 Allen key, unwind the access cover and keep at hand. SEE IMAGE 45 STEP 3 Apply thread tape or equivalent to a Pete’s Plug (Enware part ATMS1221) and thread into the 1/4” thread port. SEE IMAGE 46 IMAGE 45 STEP 4 Insert measurement probe into Pete’s Plug and open isolation...
  • Page 24 SEE IMAGE 49 CLEANING Enware Product should be cleaned with a soft damp cloth using only mild liquid detergent or soap and water. Do not use cleaning agents containing a corrosive acid, scouring agent or solvent chemicals. Do not use cream cleaners, as they are abrasive.
  • Page 25 THERMAL DISINFECTION PROCEDURE PROCEDURE FOR FLUSHING WITH HOT WATER FOR DISINFECTION Enware Product Code: ATMS698 eSQX Bypass Adaptor Kit The internal components can be flushed with full hot water temperature by adding a bypass to Strainer / Check Valve Assembly ports, using the following procedure.
  • Page 26 Restore hot and cold water supplies by opening the integral isolation valves. STEP 15 Fit front plate and spout back on. STEP 16 Commission the valve and set the valve to required temperature, according to the Commissioning Procedure on page 16. Call 1300 369 273 www.enware.com.au...
  • Page 27: Changing The Sensor Program

    MAXIMUM 5 SECS STEP 5 Once the program is chosen, wait for 5 seconds. The LED will blink back to confirm the program number it is set to. The sensor is now set www.enware.com.au Call 1300 369 273...
  • Page 28: Program - Active Sensor

    – – – Automatic flow 12h ON – – – SENSITIVITY LEVEL 3 Least sensitive for 1 Most sensitive 2 Less sensitive for difficult the most difficult light light conditions or conditions or interference interference Call 1300 369 273 www.enware.com.au...
  • Page 29: Program - Wave On/Off

    15 second lock out time after off Nurse mode A 20-100mm 10 sec ON 30 sec OFF 20 sec ON Automatic Flow OFF – – – – – Automatic Flow 12h ON – – – – – www.enware.com.au Call 1300 369 273...
  • Page 30: Troubleshooting

    Technical Table Strainers contain debris Clean strainers ensuring debris is removed Water is leaking Mixer body o-rings are worn or Replace sealing o-rings from mixer body damaged Fitting connections have loosened Tighten all connections and threads, ensure they are sealed Call 1300 369 273 www.enware.com.au...
  • Page 31 Mixed water Thermostatic cartridge contains Clean the Cartridge ensuring that all debris is temperature doesn’t debris, has failed or is damaged removed and components are not damaged. change when the Replace if necessary temperature cam is rotated www.enware.com.au Call 1300 369 273...
  • Page 32 Follow steps in Maintenance and Servicing solenoid valve/ sensor/ battery/ instructions and replace if needed power supply Power supply is turned off Turn on power supply Sensor is constantly activated by Remove interfering object an object in front of sensor Call 1300 369 273 www.enware.com.au...
  • Page 33: Product Warranty

    3 Years warranty, parts supply only is applicable to the thermostatic cartridge component assembly. If the valve is sold by a party other than ENWARE then it is sold by that seller as principal and the seller has no authority from ENWARE to give any additional warranty on behalf of ENWARE.
  • Page 34: Commissioning And/Or Maintenance Report

    2. The valve manufacturer / 3. The Australian Standards authority supplier requirements for Plumbing and Drainage  YES  NO  YES  NO  YES  NO If NO, give details and action taken: Call 1300 369 273 www.enware.com.au...
  • Page 35 Previous service carried out by: Date of previous service: Valve installed by: Date of installation: It is hereby certified that all the commissioning work has been carried out by the undersigned in accordance with local plumbing requirements for Thermostatic Mixing Valves Contractor Business Name Contractor Lic/Cert No Contractor Name (print) Signature Licensed Plumber Contractors Phone No Date Owner/Occupier Signature Date NOTE: A duplicate copy of this report is to be retained at the site for any inspection by authorised persons www.enware.com.au Call 1300 369 273...

Table of Contents