To update a Machine Edition project
You can update a Machine Edition application currently stored on the
QuickPanel View with a revision stored on a flash device, such as a CF card.
1. Insert the flash device containing an upgraded version of the Machine
Edition project into the appropriate port.
2. Reboot the machine (see page 2-11).
See the settings section below, as depending on options set, the update
may or may not be enabled, or may automatically update. If there is
more than one flash device with a valid project copy present, a Select
Media confirmation dialog will appear allowing you to choose which
flash device to update with. Select the device from the list and select OK
to continue. When a valid project is found on the flash device, you will
be prompted to install the project or skip it. Tap OK to install or Cancel
to skip the install and continue to boot. If an invalid project is found, an
error message appears in a dialog box. This dialog box must be closed
before boot will continue.
3. Remove the flash device from the port.
GFK-2306E
Chapter 2 Overview
2