[ X Troubleshooting ]
Time of data storage before error
Inlet water temp (Twi )
Outlet water temperature (Two)
Discharge refrigerant temperature TH1
Suction refrigerant temperature TH2
Shell temperature TH3
Air-side heat exchanger outlet refrigerant temperature TH4
Outside temperature TH9
Inlet water temperature TH10
Outlet water temperature TH11
External water sensor temperature 1 TH14
External water sensor temperature 2 TH15
High pressure HP
Low pressure LP
THL temperature
Water temperature setting using an external analog input (4-20 mA Current input)
I u(U-phase current)(Compressor)
I w(W-phase current)(Compressor)
I dc(Bus current)(Compressor)
V dc(Bus voltage)(Compressor)
I u(U-phase current)(Fan)
I w(W-phase current)(Fan)
I dc(Bus current)(Fan)
V dc(Bus voltage)(Fan)
Suction SH (target)
Compressor frequency (actual frequency)
Suction SH
Shell bottom SH
Operating frequency of the fan (actual frequency)
Opening of the LEV1 on the main circuit
Injection LEV opening
Discharge SH (target)
Discharge SH
Target water temperature
Water temperature setting using an external analog input (0-10 V or 2-10 V Voltage input)
Water temperature setting using an external analog input (1-5 V Voltage input)
(Note1) Each circuit board displays error data of its own unit and not other units.
(Note2) "Before error" is defined as the period between 19 minutes before the occurrence of an error up to immediately before the occurrence of the error.
(Note3) When the input type is selected. When the input type is not selected = 0
HWE22020
Item
- 132 -
Unit and circuit type
Item
LED display
code
Main unit Sub unit
c01
First decimal place
c02
First decimal place
c03
First decimal place
c04
First decimal place
c05
First decimal place
c06
First decimal place
c07
First decimal place
c08
First decimal place
c09
First decimal place
c10
First decimal place
c11
First decimal place
c12
Second decimal place
c13
Second decimal place
c14
First decimal place
c15
First decimal place
(Note3) Fixed to 0
c16
First decimal place
c17
First decimal place
c18
First decimal place
c19
Integer
c20
First decimal place
c21
First decimal place
c22
First decimal place
c23
Integer
c24
First decimal place
c25
Integer
c26
First decimal place
c27
First decimal place
c28
Integer
c29
Integer
c30
Integer
c31
First decimal place
c32
First decimal place
c33
First decimal place
c35
First decimal place
(Note3) Fixed to 0
c36
First decimal place
(Note3) Fixed to 0
Fixed to 0
Fixed to 0