[ VII Control ]

[2] Operating characteristics and Control Capabilities

Outline of Control Method
-1- Operating characteristics
Function
Unit
Pressure
protection
switch
Compressor overcurrent relay
Thermis-
tor
Refrigerant
Liquid injection circuit
circuit
control
Pump
Inlet (freeze-up protection)
control
Outside temperature thermis-
tor
Freeze-up protection circuit
HWE22020
Component
Symbol
High-pressure
63H1
switch
High-pressure
PSH1
sensor
Low-pressure
PSL1
sensor
Discharge refrig-
TH1
erant temp.
(Discharge temp.
overrise protec-
tion)
Air-side HEX out-
TH4
let temp.
(vacuum protec-
tion)
Suction temp.
TH2
(vacuum and
freeze-up protec-
tion)
Compressor shell
TH3
temp.
(compressor
floodback protec-
tion)
Water inlet temp.
TH10
Water outlet temp. TH11
LEV2
TH10
TH11
Control/
Ac-
Unit
Detection
tion
HP 63H1
ON
MPa
OFF MPa
HP PSH1
OFF MPa
LP
PSL1
OFF MPa
Compressor
OFF
A
current
Discharge
OFF
ºC
gas temp.
Air-side HEX
OFF
ºC
outlet temp.
Suction gas
OFF
ºC
temp.
Comp. shell
OFF
ºC
temp.
Water temp.
OFF
ºC
Discharge
ºC
gas temp.
Water inlet
ON
ºC
OFF
ºC
Outside
ON
ºC
temp.
OFF
ºC
- 96 -
Trigger condition
(2.95)
3.85
+0
-0.15
-
The low pressure has dropped below 0.03 MPa
within 30 seconds of compressor start-up.
The low pressure has dropped below 0.03 MPa
within 30 seconds of a defrost cycle.
During water heating, the low pressure has
dropped by 0.02 MPa after the air-side heat ex-
changer outlet temperature has reached -31ºC.
During water heating, the low pressure has
dropped by 0.02 MPa after the air-side suction
pipe temperature has reached -33ºC.
The outside temperature of 10ºC or above has
been detected for 20 minutes and the low pres-
sure has dropped below 0.03 MPa during water
heating.
56
A discharge gas temperature of 110ºC or above
has been detected for 30 seconds while the com-
pressor is in operation. (Preliminary abnormal
stop)
If this happens three times, the unit will make an
abnormal stop.
If a discharge gas temperature of 115ºC or above
was detected, the unit will make an abnormal
stop.
An air side heat exchanger outlet temperature of
-33ºC was detected.
A suction gas temperature of -36ºC was detected.
A shell bottom SH temperature of 10ºC or below
has been detected for 40 minutes while the com-
pressor is in operation.
When the inlet water temperature or outlet water
temperature detects Tmax or higher Tmax is 70ºC
when the outdoor air temperature is -20ºC or high-
er, and 65ºC when the outdoor air temperature is -
25 ºC. The outdoor air temperature during that time
is linearly interpolated.
Injection is controlled by referencing the discharge
gas temperature.
3
5
1
3
The pump turns on when the water inlet tempera-
ture has reached below the "ON" threshold AND
the outside temperature has reached below the
"ON" threshold when the compressor is stopped.
GB