P.16.50
Relay Word Bits
Row List
Table 16.2 Row List of Relay Word Bits (Sheet 12 of 35)
Row
Name
95
87LUA, 87LUB, 87LUC
95
87LU
95
87DD
96
87L50A, 87L50B, 87L50C
96
87L50Q
96
87L50G
96
87EFDL
96
87EFDR
96
87EFD
97
87DDL
97
87DDR
97
87CCC
97
87CCB
97
87CCD
97
87CCU
97
87CTWL
97
87CTXL
98
87MTR
98
87SLV
98
87LST
98
87CH1OK, 87CH2OK,
87CH3OK
98
87SYNH
98
87SYNL
99
87HSB
99
87CH1T, 87CH2T,
87CH3T
99
87CH1DT, 87CH2DT,
87CH3DT
99
87TEST
Local Bits
100
LB01–LB08
101
LB09–LB16
102
LB17–LB24
103
LB25–LB32
SEL-411L Relay
Bit Description
87L phase element, unrestrained (high-set) overcurrent element operated in the A-phase,
B-phase, C-phase (with in-line transformer, only)
87L phase element, unrestrained (high-set) overcurrent element operated in any phase
(with in-line transformer, only)
Disturbance detected (local and remote)
87L phase element, A-phase, B-phase, C-phase overcurrent supervision picked up
87L negative-sequence element, overcurrent supervision picked up
87L zero-sequence element, overcurrent supervision picked up
External fault detected at the local terminal
External fault detected by one of the remote terminals
External fault detected in a vicinity of the protected line
Disturbance detected in local 87L currents or LINEV voltages
Disturbance detected in remote currents
Charging current compensation applied to local terminal currents using the local voltage
(87CCC must = 87CCB + 1)
Best possible charging current compensation (87CCB must = 87CCD + 1)
Charging current compensation degraded (87CCD must = 87CCU + 1)
Charging current compensation (87CCU, CCD, CCB and CCC must all be in the same
LongWord)
Terminal W included in 87L element
Terminal X included in 87L element
The 87L function is in the master mode; the differential current is calculated.
The 87L function is in the outstation mode; the differential current is not calculated, but
the 87L function is operational owing to the 87 DTT.
The 87L function is not available (is lost). The relay is not in the master mode and will not
trip via 87 DTT because the DTT is disabled, or none of the connected relays is in the
master mode.
Communication on Channel 1–3 is OK
The 87L system synchronized with high precision
Synchronization of the 87L system potentially degraded
Hot stand-by channel switch (if deasserted the 87PCH used; if asserted, the other channel
is used)
Maximum channel delay alarm for Channel 1–3
Step change in the round trip alarm for Channel 1–3
87L function in a test mode
Local Bits 1–8
Local Bits 9–16
Local Bits 17–24
Local Bits 25–32
Protection Manual
Date Code 20151029