Electromagnetic Compatibility (Emc) - ABB VICPAS CP660-x Operating Instructions Manual

Hide thumbs Also See for VICPAS CP660-x:
Table of Contents

Advertisement

Electromagnetic Compatibility (EMC)

Test executed on the 230 V AC side of the Power Supply (EN 61000-4-11).
Parameter
Emitted interference
Electrostatic
Immunity to radiated radio-
frequency
Electromagnetic field
Immunity to conducted dis-
turbances inducted by radiof-
requency field
Fast transient
Input and output AC power
ports
Signal port
Immunity to conducted dis-
turbances inducted by radiof-
requency field
Voltage dips, short interrup-
tions and voltage variations
immunity test
Electrostatic discharge
PC/Printer Port – COM2
PLC Port – COM1
AUX Port
User memory
Recipe memory
Hardware clock
Accuracy RTC (at 25°C
operating)
Operating Instructions
Value
Class A
8 kV (air electrostatic discharge)
4 kV (contact electrostatic discharge)
80 MHz ... 1 GHz, 10 V/m
1 GHz ... 2 GHz, 3 V/m
2 GHz ... 2.7 GHz, 1 V/m
900 MHz, 10 V/m
0.15 MHz ... 80 MHz 10 V
2 KV power supply
1 KV signal lines
Level: 2 kV (L1/L2-PE) 1 kV (L1-L2)
Level: 1 kV (line to earth)
0.15 ... 80 MHz, 10 V
Port: AC mains.
Level: 0 % / duration: 1 cycle and 250 cycles (50 Hz) or
300 cycles (60 Hz);
40 % / duration: 10 cycles (50 Hz) or 12 cycles (60 Hz);
70 % / duration: 25 cycles (50 Hz) or 30 cycles (60 Hz);
Phase: 0°-180°
8 kV in air
RS-232, RS-485, RS-422 software configurable
300 ... 38400 baud
RS-232, RS-485, RS-422 software configurable
300 ... 38400 baud
Connector DB-9 pin female (functionality can be config-
ured with an optional communication module)
Flash 128 Mb
32 kB FRAM
Clock/calendar with back-up battery
< 100 ppm
8
According to
EN 55011
EN 61000-4-2
EN 61000-4-3
EN V 50204
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-2
CP650, CP660, CP675

Advertisement

Table of Contents
loading

Table of Contents