Phasor measurement unit RES670
Version 2.2
IEC140000122 V4 EN-US
Figure 2. Block diagram for configuration A20
Description of configuration B20
The configuration of the IED is shown in
RES670 B20 configuration is applicable for a typical double
busbar single breaker arrangement monitoring up to six
bays. RES670 B20 is delivered in ¾, and full (1/1)19" rack
casing. For this application 24 analog inputs are used, thus
two transformer modules (TRM) with 12 analog inputs (9I
+3U) per TRM are available in B20 standard configuration.
As shown in
figure
3, RES670 B20 configuration as a PMU
is measuring two 3-phase voltages of the busbars and six 3-
phase currents of bays 1 to 6. There are two instances of
PMU reporting functionality available in B20 configuration,
meaning two independent IEEE C37.118/1344 data
streams. Each instance of PMU is reporting frequency-
deviation and rate-of-change-of-frequency data. In the
standard B20 configuration, in addition to frequency data,
Hitachi Energy
BAY03_CT
BAY02_CT
BAY01_CT
Other Functions available from the function library
71
DELTAI
7V_78V
DELTAU
DELI SPVC
DELV SPVC
71
3
Control
S SIML
S XCBR
Optional Functions
87
INd/I
ITHD
ITHD
CHM MHAI
CCS SPVC
78
Ucos
51_67 4(3I>)
OOS PPAM
OC4 PTOC
figure
3.
first instance of PMU (first data stream) is reporting 32
synchrophasors over IEEE C37.118/1344; that is eight 3-
phase synchrophasors and 24 single phase synchrophasors
corresponding to the AC voltage and current
measurements. Second instance of PMU (second data
stream) is reporting 16 synchrophasors over IEEE
C37.118/1344; that is four 3-phase synchrophasors and 12
single phase synchrophasors corresponding to the AC
voltage and current measurements. The number of
synchrophasor reporting channels on second instance of
PMU can be extended to 32 channels per request. This can
be done when ordering the RES670 B20 configuration.
In addition, each data stream includes 16 analog and 16
binary reporting channels over IEEE C37.118/1344 in the
standard configuration. The number of analog and binary
© 2017 - 2022 Hitachi Energy. All rights reserved
RES670 A20 – Phasor Measurement Unit, 3 bays, single busbar,
WA1_VT
WA1
DFR/SER DR
DRP RDRE
MET
P/Q
MET
I
CV MMXN
C MMXU
MET
P/Q
MET
I
CV MMXN
C MMXU
MET
P/Q
MET
I
CV MMXN
C MMXU
MET W/Varh
3
Control
7
DELTA
DEL SPVC
ETP MMTR
Q CBAY
MET
UN
VN MMXU
4(IN>)
U>/I<
2(I>/U<)
51N_67N
CV GAPC
EF4 PTOC
FUF SPVC
67N
IN>
VTHD UTHD
68
Zpsb
SDE PSDE
VHM MHAI
ZMBU RPSB
1MRK 511 410-BEN P
12AI (9I+3U)
81
df/dt
SA PFRC
81
f>
SA PTOF
81U
f<
SA PTUF
27
2(3U<)
UV2 PTUV
59
2(3U>)
OV2 PTOV
MET
U
V MMXU
MET
Usqi
V MSQI
IEEE Std 1344
PMU REP
IEEE Std C37.118
MET
Isqi
C MSQI
Phasor
data
IEEE Std 1344
MET
Isqi
C MSQI
PMU REP
IEEE Std C37.118
MET
Isqi
C MSQI
94
1→0
63
SMP PTRC
S SCBR
S SIMG
32
P>
37
P<
46I2
4(I2>)
NS4 PTOC
GOP PDOP
GUP PDUP
IEC140000122-4-en.vsdx