Hitachi Relion 670 Series Product Manual page 45

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Phasor measurement unit RES670
Version 2.2
Binary inputs and outputs
Table 12. BIM - Binary input module
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
Counter input frequency
Oscillating signal discriminator
*Debounce filter
Binary input operate time
(Debounce filter set to 0 ms)
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
Table 13. BIM - Binary input module with enhanced pulse counting capabilities
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V
48/60 V
110/125 V
220/250 V
Counter input frequency
Balanced counter input frequency
Oscillating signal discriminator
*Debounce filter
Binary input operate time
(Debounce filter set to 0 ms)
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
Hitachi Energy
M12576-1 v13
Rated value
16
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
10 pulses/s max
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Settable 1–20 ms
3 ms
M50609-2 v10
Rated value
16
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
10 pulses/s max
40 pulses/s max
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Settable 1-20 ms
3 ms
© 2017 - 2022 Hitachi Energy. All rights reserved
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
-
-
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
-
-
-
1MRK 511 410-BEN P
IP15844-1 v1
45

Advertisement

Table of Contents
loading

This manual is also suitable for:

Res670

Table of Contents