Hitachi Relion 670 Series Product Manual page 53

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Phasor measurement unit RES670
Version 2.2
Table 22. Auxiliary DC supply voltage influence on functionality during operation
Dependence on
Ripple, in DC auxiliary voltage
Operative range
Auxiliary voltage dependence, operate
value
Interrupted auxiliary DC voltage
Interruption
interval
0–50 ms
0–∞ s
Restart time
Table 23. Frequency influence (reference standard: IEC 60255–1)
Dependence on
Frequency dependence, operate value
Harmonic frequency dependence (20% content)
Hitachi Energy
Reference value
Within nominal
range
max. 2%
15% of EL
Full wave rectified
±20% of EL
24-60 V DC ± 20%
90-250 V DC ± 20%
Within nominal range
f
r
f
r
2
© 2017 - 2022 Hitachi Energy. All rights reserved
Influence
0.01%/%
0.01%/%
No restart
Correct behaviour at power down
< 300 s
±2.5 Hz for 50 Hz
±3.0 Hz for 60 Hz
nd
rd
th
, 3
and 5
harmonic of f
r
1MRK 511 410-BEN P
Influence
±1.0%/Hz
±2.0%
53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Res670

Table of Contents