6.4 NFPA Style D IDC Using Monitor Modules

Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each FMM-1 module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address.
Figure 6.7 shows typical wiring for a supervised and power-limited NFPA Style D (Class A) IDC using the FMM-1 module.
Module installation notes:
1.
The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamps @ 24 VDC (nominal).
2.
The IDC provides the following services (do not mix):
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervisory service with normally open contact devices
• Security service
3.
Refer to the Device Compatibility Document for compatible smoke detectors.
4.
See Appendix A, "Power Considerations", on page 58 for information on supervising 24 VDC power.
36
Manual pull
station
Heat
detector
Figure 6.6 Typical Style B IDC Wiring with FMM-1
NFPA Style D IDC Using Monitor Modules
24 VDC
Four-wire
Detector Base
47K ELR
(supplied
with module)
IDC
FMM-1
Notifier SLC Wiring Manual — P/N 51253:U5 12/20/2017
From Supply
24 VDC Power
Filtered, Regulated,
Resettable
To Next IDC
or
Supervision Device