Chapter 6. Diagnostics
Channel
Diagnosis
Error
AlarmType
Type
Channel Diagnosis
270
Appears/Disappears
Channel Diagnosis
271
Appears/Disappears
Channel Diagnosis
272
Appears/Disappears
Channel Diagnosis
273
Appears/Disappears
Channel Diagnosis
274
Appears/Disappears
Channel Diagnosis
275
Appears/Disappears
Channel Diagnosis
276
Appears/Disappears
Channel Diagnosis
277
Appears/Disappears
Channel Diagnosis
278
Appears/Disappears
Channel Diagnosis
279
Appears/Disappears
Channel Diagnosis
280
Appears/Disappears
64
Module or
Channel
Cause
Error
Automatically
Channel
restart after a fatal
error occurred
Loss of power input
Module
1 fault
Loss of power input
Module
2 fault
Loss of terminal
Module
block fault
The module internal
temperature
Module
exceeds the
allowable limit.
Module output
Module
default mode
mismatch
Channel output has
Channel
no load
Channel
Short to power fault Short to power
Channel output
Channel
over load
Channel
Switch fail fault
Channel pulse test
Channel
failed
PACSystems* RX3i CEP PROFINET Scanner
Fault Text
Recommended Action
There are no corrective
actions for this.
Restart after
Successfully restarting
fatal error.
RX3i CEP module again
may eliminate the fault.
Verify field power to the
power input 1 is wired
and energized. If there did
Loss of RX3i CEP
expect no power, set
power input 1
power supply
configuration to Single in
configuration tool.
Verify field power to the
power input 1 is wired
and energized. If there did
Loss of RX3i CEP
expect no power, set
power input 2
power supply
configuration to Single in
configuration tool.
Verify the terminal block
Loss of terminal
is installed on specified
block
module.
Over
Decrease the
temperature
temperature.
Check the hardware
Module output
configuration and DIP
default
switch on the back of
mismatch
module.
Open load
Correct wiring, verify load
detected
on specified channel.
Verify input source and
channel input type
configuration.
Correct wiring, verify load
Circuit Overload
on specified channel.
There are no corrective
Switch Failure
actions for this. Try power
cycle the module.
There are no corrective
Pulse Test
actions for this. Try power
Failure
cycle the module.
GFK-2883E