Fatal Error Handling; Automatic Restart - GE PACSystems RX3i User Manual

Cep profinet scanner
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

6.3 Fatal Error Handling

Any failures that occur during power-up or firmware update mode are considered fatal errors. This includes
faults detected on non-critical devices such as the USB port. After successful powerup of the RX3i CEP, only
catastrophic errors are treated as fatal. When a fatal error occurs, the RX3i CEP blinks an error code on its
LEDs, then stays in blinking mode or automatically restarts according to its Fatal Error Action. For example, a
blink code of 4-5 is a Watchdog error. This may be expected during heavy network traffic.
Certain conditions can prevent the module from powering up and becoming operational or entering firmware
update mode:
For LED behavior, refer to section 2.2.1,
Problem
Hardware failure
Invalid firmware
Power-up diagnostics/
hardware initializations fail
that are considered fatal
Catastrophic error during
operation

Automatic Restart

If the RX3i CEP is configured to automatically restart after a fatal error, on the next successful power-up, a
diagnosis alarm is generated to indicate the RX3i CEP reset. This diagnosis alarm turns the Fault LED on and
persists until the RX3i CEP is power-cycled. There is no way to clear this fault other than a second successful
restart.
This might be a preferable setting under certain conditions. For example, if you are experiencing repeated 4-5
Watchdog errors, you could use this setting to automatically recover.
A persistent fatal error that occurs after the RX3i CEP has successfully powered-up can cause the module to
continually reset itself. Please record the blink code and contact customer service for this case.
GFK-2883E
Fatal Error
Codes.
Indication
OK LED is off
Enter boot mode, OK, CONN, PORT1 and PORT2
LED flash green in unison
LED Fatal Error blink code or automatic restart
after the blink code appears once
LED Fatal Error blink code or automatic restart
after the blink code appears once
March 2018
Chapter 6. Diagnostics
Action
Contact Customer Service.
Return the module to GE
Automation & Controls
Update firmware to latest
version
Note the blink code and
contact Customer Service
Note the blink code and
contact Customer Service