Huawei FusionDC1000A40 Quick Manual page 11

Prefabricated all-in-one data center 2021, zambia, zesco

Advertisement

No.S002 Pre-fab. Module Grounding Position Diagram
Note:
1. Four ground points are set for each pre-fab. module, among which two are located
at the front wall and two at the rear wall. For details about the ground points, see the
figure above. The ground points are connected with the ground grid. Before
grounding, remove the aluminum foil from the ground points. The ground bolts are
M12×30 stainless steel hexagon bolts with a torque of 60 N·m.
540
1,026
1,026
Drawing No.
Quantity
Item
Ground
4
GB5783-2000_M12X30_S_ZNALL
screw
Unit
PCS