Space Heating / Space Cooling Configuration - Hitachi RWM-2R1E Installation & Operation Manual

And yutaki cascade controller
Hide thumbs Also See for RWM-2R1E:
Table of Contents

Advertisement

YUTAKI CASCADE CONTROLLER

8.13.3.4 Space Heating / Space Cooling configuration

Control the temperature for Space Heating or Space Cooling by configuring the following parameters.
Water calculation mode:
Selection of the water set point for
Circuit 1 or Circuit 2 (Space Heating
or Space Cooling).
Deactivated
Points
Gradient (only in heating mode)
Fix
See detailed explanation below.
Eco Offset Water setting:
Configure the offset water temperature
for the ECO mode for Space Heating
or Space Cooling.
By using this function, current water
temperature setting is reduced by the
indicated parameter.
Range: 0 ~ 10
134
PMML0575 rev.1 - 09/2021
Working Limits:
Limit for the temperature set-point to
prevent high or low temperatures at
Space Heating or Space Cooling:
Maximum supply temperature
Minimum supply temperature
Mixing valve:
To control the second water temperature (only for
circuit 2).
Values are adjusted for the use with the 2nd zone
mixing kit accessory ATW-2KT-05. It is highly
recommended not to change these values.
In case of using a mixing kit different from the
ATW-2KT-05 configure the following parameters:
Proportional band: 0~20K (6.0 K by default).
Integral reset factor: 0.0~20% (2.5 % by default).
Running time factor: 10~250 sec (140 sec by
default).
Over temperature offset protection: OFF, 3~10ºC
(5 ºC by default).