Page 3
:- 07/09/18 UNPACKING Carefully remove the PD120 dehumidifier unit from its transit box and visually check for signs of transit damage. If there is evidence of damage DO NOT attempt to operate the unit, call your supplier for advice. Do not discard the packing, it will be useful when transporting the dehumidifier unit in the future.
OWER OWER UPPLY UPPLY UPPLY UPPLY F F F F : : : : Powder-coated Epoxy INISH INISH INISH INISH R R R R T T T T : : : : R407c EFRIGERANT EFRIGERANT EFRIGERANT EFRIGERANT PD120 OWNERS MANUAL...
Before connecting this unit to the relevant power supply the following must be carried out. Selecting the correct fan speed – The PD120 has a low fan speed and a high fan speed and the required speed must be chosen before installation. To select the correct fan speed firstly remove the air outlet cover via the 10off M4 hex head bolts, then remove the electrical box cover via the 4off M4 hex head bolts.
Page 6
:- 07/09/18 OPERATION The following procedures should be followed to test the PD120 for correct operation: 1) After unpacking, examine all external features to confirm damage-free shipment. Report all defects and damage at once. Connect the power cable to a grounded power source.
Partial frosting accompanied by frosting of the thin capillary tubes, indicates loss of refrigerant gas or low charge. Check all wiring connections. F ANY OF THE PRECEDING PROBLEMS OCCUR CONTACT THE ERVICE ENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO PREVENT PERMANENT DAMAGE PD120 OWNERS MANUAL...
Page 8
An open circuit indicates that the compressor should be replaced. c. Check that the compressor is not grounded by establishing that a circuit does not exist between the compressor terminals and the shell of the compressor. PD120 OWNERS MANUAL...
2. Ensure that no section of the drain 2. Drain pipe too high hose is above the level of the water machine outlet Ebac Industrial Products, Inc. 700 Thimble Shoals Blvd, Suite 109 Newport News, VA. 23606-2575 Tel: (757) 873 6800 Fax: (757) 873 3632 Website www.ebacusa.com...
V V V V : : : : ONTROL ONTROL OLTAGE OLTAGE ONTROL ONTROL OLTAGE OLTAGE T T T T D D D D F F F F : : : : 15 A ELAY ELAY ELAY ELAY PD120 OWNERS MANUAL...
Page 11
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed. The Global Warming Potential (GWP) of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a – 1300 R407c – 1610...