System Sensor DH400ACDCP Installation And Maintenance Instructions Manual
System Sensor DH400ACDCP Installation And Maintenance Instructions Manual

System Sensor DH400ACDCP Installation And Maintenance Instructions Manual

Air duct smoke detector

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
DH400ACDCP Air Duct Smoke Detector
Before Installing
Please thoroughly read the System Sensor Guide for Proper
Use of Smoke Detectors in Duct Applications (A05-1004),
which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies
of this manual are available online at www.systemsensor.
com or via System Sensor's toll free fax-back service, Docu-
ments on Demand at 800/736-7672. NFPA Standards 72 and
90A should also be referenced for detailed information.
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: This detector must be tested and maintained
regularly following NFPA 72 requirements. The detector
should be cleaned at least once a year.

Table of Contents

List of Tables and Figures
Fig. 1:
Duct Detector Exploded View
Fig. 2:
Installation of Sampling Tube Gaskets
Fig. 3:
Mounting Location of Speed Nuts
Table 1: Inlet Sampling Tube Selection
Fig. 4:
Inlet Sampling Tube
Fig. 5:
Sampling Tube Mounting Configurations
Fig. 6:
Sampling Tube Filter Installation
Fig. 7:
Wiring Diagram
Fig. 8:
Wiring Diagram - No Control Panel
Fig. 9:
Wiring Diagram - Accessories
Fig. 10: Testing Detector Alarm
Fig. 11: Detector Head Removal
Fig. 12: RTS451/RTS451KEY Test Coil Installation
Fig. 13: Photo Head Exploded View
D400-13-00

[1] General Description

An HVAC system supplies conditioned air to virtually ev-
ery area of a building. Smoke introduced into this air duct
system will be distributed to the entire building. Smoke
detectors designed for use in air duct systems are used to
sense the presence of smoke in the duct.
Model DH400ACDCP Air Duct Smoke Detector utilizes pho-
toelectric technology for the detection of smoke. This smoke
detection method, when combined with an efficient hous-
ing design, samples air passing through the duct and allows
detection of a developing hazardous condition. When suf-
ficient smoke is sensed, an alarm signal is initiated at the
fire control panel monitoring the detector, and appropriate
action can be taken to shut off fans and blowers, change
over air handling systems, etc. These actions can facilitate
Page
the management of toxic smoke and fire gases throughout
1
the areas served by the duct system.
2
DH400ACDCP detectors are designed to operate from 24
2
VDC, 24 VAC, 120 VAC, or 240 VAC. Alarm and supervisory
2
relay contacts are available for control panel interface (alarm
initiation), HVAC control, and other auxiliary functions.
2
These detectors are not designed for 2-wire application.
5
For testing, the alarm can be enabled by a magnet activated
9
test switch, by insertion of a calibrated test card into the
11
sensing chamber (photoelectronic version only), or by the
12
optional remote test station. The duct smoke detectors latch
16
into alarm state when alarm occurs. LEDs on each detector
Page
illuminate to provide local alarm indication, and optional
accessories offer a variety of annunciation capabilities.
2
The detector can be reset by a momentary power inter-
3
ruption, by the magnet activated reset switch, or by the
3
optional remote test station.
3
4
4
5
6
7
8
9
9
10
10
1
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsenor.com
I56-0555-010R

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DH400ACDCP and is the answer not in the manual?

Questions and answers

Summary of Contents for System Sensor DH400ACDCP

  • Page 1: Table Of Contents

    Copies of this manual are available online at www.systemsensor. com or via System Sensor’s toll free fax-back service, Docu- ments on Demand at 800/736-7672. NFPA Standards 72 and 90A should also be referenced for detailed information.
  • Page 2: Exploded View Of Duct Detector Components

    System Sensor supports this position and strongly recom- mends that the user read NFPA Standards 90A, 72, and 101. The DH400ACDCP Air Duct Smoke Detectors are listed per UL 268A. D400-13-00...
  • Page 3 [5.1] Verify Duct Air Flow Direction And Velocity Model DH400ACDCP detectors are designed to be used in air handling systems having air velocities of 500 to 4000 feet per minute. Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these parameters.
  • Page 4 Figure 4. Air duct detector inlet sampling tube: AIR HOLES FLANGE MUST FACE INTO AIR FLOW Figure 5. Tube mounting configurations with varying air flow direction: AIR FLOW DIRECTION DETECTOR HOUSING AIR FLOW DIRECTION DETECTOR HOUSING [5.4.2] Installation For Ducts More Than 8 Feet Wide NOTE: To install inlet tubes in ducts more than 8 feet wide, work must be performed inside the air duct.
  • Page 5: Duct Detector Maintenance And Test Procedures

    See Section [6] for more information. Replacement filters can be ordered from System Sensor, 3825 Ohio Ave., St. Charles, IL 60174. (Ex- haust tube/intake tube filter P/N F36-05-00). [5.7] Perform Detector Check 1.
  • Page 6 Figure 7. System wiring diagram for duct detectors using a UL listed control panel (see Figure 9 for wiring of optional accessories): CAUTION Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections. H0252-00 D400-13-00 I56-0555-010R...
  • Page 7 SIGNAL TROUBLE CONDITION TO PANEL. (+) ALARM SIGNAL (–) AUX POWER (+) AUX POWER TROUBLE CONTACTS DH400ACDCP DUCT DETECTOR POWER INPUTS ACCEPT 24 VDC, 24 VAC 50-60 HZ, 120 VAC 50-60 HZ, OR 220/240 VAC 50-60 HZ. CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR.
  • Page 8 The RTS451/RTS451KEY Remote Test Station facilitates test of the alarm capability of the duct detector as indicated in the RTS451/RTS451KEY manual. The DH400ACDCP duct detector can be reset by the RTS451/RTS451KEY. If a system control panel is used, the panel itself may also require resetting.
  • Page 9: Detector Cleaning Procedures

    Figure 10. Testing detector alarm: DETECTOR HEAD TEST TEST MAGNET LOCATOR PAINTED SIDE TOWARD HOUSING To install the RTS451/RTS451KEY, connect the device as shown in Figure 8; wire runs must be limited to 25 ohms or less per interconnecting wire. Place the coil in the detector housing with the arrow facing up and pointing toward the detector as in Figure 12.
  • Page 10 Figure 12. RTS451/RTS451KEY test coil installation: TEST COIL DETECTOR [7.2] Photo Heads 1. Remove the detector cover by inserting a small bladed screwdriver into the slot located 90 degrees from the field test port. Rotate the cover counterclockwise to re- move (see Figure 13).
  • Page 11: Specifications

    [8] Model DH400ACDCP Air Duct Smoke Detector Specifications Description HVAC air duct mounted ionization or photoelectronic smoke detector for separately powered systems or stand alone sys- tems. Auxiliary alarm relay contacts provide fan contactor shutdown to prevent HVAC circulation of smoke.
  • Page 12: Warranty

    0.3A @ 32 VDC (resistive) Please refer to insert for the Limitations of Fire Alarm Systems System Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for the enclosed product.
  • Page 13 NOTES D400-13-00 I56-0555-010R...
  • Page 14 NOTES D400-13-00 I56-0555-010R...
  • Page 15 NOTES D400-13-00 I56-0555-010R...
  • Page 16: Detector Test Log

    _______ ______________ _______ ______________ _______ ______________ _______ ______________ _______ ______________ _______ ______________ _______ ______________ _______ ______________ _______ ______________ Date Comments ___________________________ ___________________________ ___________________________ ___________________________ ___________________________ ___________________________ ___________________________ ___________________________ ___________________________ ___________________________ ___________________________ ___________________________ ___________________________ ___________________________ ___________________________ ___________________________ I56-0555-010R ©2006 System Sensor...

Table of Contents