Air duct smoke detector with extended air speed range

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
DH100ACDCLP Air Duct Smoke Detector
with Extended Air Speed Range
The Innovair DH100ACDCLP model is a photoelectric
detector approved for an extended air speed range of 100 to
4000 feet per minute (0.5 m/s to 20.3 m/s) and an opera-
tional temperature range of 32°F to 131°F (0°C to 55°C).
Before Installing
Please thoroughly read the System Sensor Guide for Proper
Use of Smoke Detectors in Duct Applications (I56-473),
which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies
of this manual are available from System Sensor. NFPA
Standards 72 and 90A should also be referenced for detailed
information.
NOTICE: This manual shall be left with the owner/user of
this equipment.
IMPORTANT: This detector must be tested and maintained
regularly following NFPA 72 requirements. The detector
should be cleaned at least once a year.

Table of Contents

[1] General Description ...................................................... 1
[2] Limitations of Duct Smoke Detectors ..............................1
[5] Installation Sequence .....................................................2
[7] Detector Cleaning Procedures.........................................7
[8] Board Replacement ........................................................8
[9] Specifications ................................................................8
Warranty ............................................................................8

[1] General Description

An HVAC system supplies conditioned air to virtually every
area of a building. Smoke introduced into this air duct sys-
tem will be distributed throughout the entire building.
Smoke detectors designed for use in air duct systems are
used to sense the presence of smoke in the duct.
Model DH100ACDCLP Air Duct Smoke Detector utilizes
photoelectric technology for the detection of smoke. This
detection method, when combined with an efficient hous-
ing design, samples air passing through the duct and allows
detection of a developing hazardous condition. When suf-
ficient smoke is sensed, an alarm signal is initiated and
appropriate action can be taken to shut off fans, blowers,
change over air handling systems, etc. These actions can
facilitate the management of toxic smoke and fire gases
throughout the areas served by the duct system.
The DH100ACDCLP detector is designed to operate on 24
VDC/VAC, 120 VAC, or 240 VAC. Alarm and supervisory
relay contacts are available for control panel interface (alarm
initiation), HVAC control, and other auxiliary functions.
D200-14-00
Auxiliary relays are also provided for fan shut down or sig-
naling of up to 9 other detectors in the loop for multiple fan
shut down. These detectors are not designed for 2-wire
applications.
For testing, the alarm can be enabled by a magnet activated
test switch or by the optional remote test station. The duct
smoke detector latches into alarm state when an alarm
occurs. A green LED flashes to indicate power, a red LED
signals local alarm indication, and optional accessories
offer a variety of annunciation capabilities.
The DH100ACDCLP can be reset by a momentary power
interruption, the reset button on the front cover, the control
panel, or remote reset accessory. The DH100ACDCLP
incorporates a cover tamper feature that provides a trou-
ble signal after 20 minutes if the cover is removed or
improperly installed. Proper installation of the cover
removes the trouble condition.
Page

[2] Limitations Of Duct Smoke Detectors

The National Fire Protection Association has established that
DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE
FOR OPEN AREA DETECTOR PROTECTION as a means of
providing life safety. Nor are they a substitute for early warn-
ing in a building's regular fire detection system.
System Sensor supports this position and strongly recom-
mends that the user read NFPA Standards 90A, 72, and 101.
The DH100ACDCLP Air Duct Smoke Detectors are listed per
UL 268A.
This device will not operate without electrical power.
Fire situations may cause an interruption of power. The
system safeguards should be discussed with your local
fire protection specialist.
This device will not sense smoke unless the ventilation
system is operating and the cover is installed.
For this detector to function properly, it MUST be installed
according to the instructions in this manual. Furthermore,
the detector MUST be operated within ALL electrical and
environmental specifications listed in this manual. Failure
to comply with these requirements may prevent the detec-
tor from activating when smoke is present in the air duct.
1
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
WARNING
WARNING
WARNING
WARNING
I56-0084-00

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Innovair DH100ACDCLP and is the answer not in the manual?

Questions and answers

Summary of Contents for System Sensor Innovair DH100ACDCLP

  • Page 1: Table Of Contents

    For testing, the alarm can be enabled by a magnet activated Before Installing Please thoroughly read the System Sensor Guide for Proper test switch or by the optional remote test station. The duct Use of Smoke Detectors in Duct Applications (I56-473),...
  • Page 2: Exploded View Of Duct Smoke Detector Components

    [3] Figure 1: Exploded View Of Duct Smoke Detector Components FOAM GASKETS CONDUIT HOLES DETECTOR SAMPLING TUBE HOUSING FILTERS PLASTIC TERMINAL STRIP SAMPLING TUBE POWER BOARD PLASTIC SAMPLING TUBE SELF-TAPPING SCREW COVER MOUNTING SCREWS DETECTOR BOARD DETECTOR COVER [4] Contents Of The Duct Smoke Detector Kit [5.2.1] Sampling Tube Installation for Ducts Less 1.
  • Page 3 Figure 3. Installation of foam gaskets over sampling 2. Slide the tube into the housing bushing that meets the tube bushings: air flow first. Position the tube so that the arrows point into the air flow. SCREW HOLES FOR ATTACHING HOUSING 3.
  • Page 4 Replacement filters can be ordered some of the sampling holes so that there are a total from System Sensor, 3825 Ohio Ave., St. Charles, IL 60174. of 10 to 12 holes spaced as evenly as possible (Exhaust tube/intake tube filter P/N F36-09-11) across the width of the duct.
  • Page 5: Duct Smoke Detector Maintenance And Test Procedures

    Wiring Instructions manometer to measure differential pressure between the The DH100ACDCLP detectors are designed for easy wiring. sampling tubes. Spray aerosol smoke* into the duct through ″ hole for five seconds. Wait two minutes for the duct The housing provides a terminal strip with clamping plates. ⁄...
  • Page 6 Figure 7. System wiring diagram for 4-wire duct smoke detectors: CAUTION Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections. A78-2352-11 Figure 8. Wiring diagram for DH100ACDCLP Figure 9. Wiring diagram for DH100ACDCLP to 4-Wire Wiring to APA451 to APA451: RTS451KEY and interconnect feature:...
  • Page 7: Detector Cleaning Procedures

    FIELD INSTALLED JUMPER [6.2.2.3] SSK451 Multi-Signaling Accessory The System Sensor SSK451 Multi-Signaling accessory com- bines a sounder feature with a key activated test and reset function. Green, amber and red LEDs provide a visual indica- tion of power, trouble, and alarm respectively. An optional strobe (PS24LO) with a smoke lens can be added to conform to the codes of certain jurisdictions.
  • Page 8: Board Replacement

    Please refer to insert for the Limitations of Fire Alarm Systems Three-Year Limited Warranty System Sensor warrants its enclosed air duct smoke detector to be free from defects #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describ- in materials and workmanship under normal use and service for a period of three ing the malfunction and suspected cause of failure.

Table of Contents