Huawei NetCol5000-A050 Quick Manual page 21

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

9.2
Setting Temperature and Humidity Parameters
1. Set Temperature and humidity control type, Control point temperature setpoint, and
Control point humidity setpoint as required onsite. Path: Settings > System Settings >
Common Settings or Settings > System Settings > T/H Sensor
2. If a T/H sensor outside the cabinet is installed, enable it. Path: Settings > System Settings >
T/H Sensor
9.3
(Optional) Setting Teamwork Control Parameters
On the home screen, choose
consisting of eight devices as an example.
Item
No.
1
Teamwork
1
group No.
System
1
address
Enable
Yes
teamwork
CAN resistor
Teamwork
Enable
function
CAN
network
MAC_CA
Networking
N
mode
network
or FE
network
Number of
systems in
8
this group
Number of
running
6
systems in
this group
Rotation
Enable
function
> Teamwork Settings. The following uses a teamwork group
Setting
2
...
1
...
2
...
No
...
Enable
...
Enable
CAN
...
network
network
MAC_CA
MAC_CA
N
network
...
network
or FE
or FE
network
network
/
...
/
...
/
...
7
8
Smart cooling product No.
A teamwork network can contain a
maximum of four groups, which can
be numbered 1 to 4 respectively.
1
1
Smart cooling products in a group
must have the same teamwork group
number.
In a teamwork group, the address (1–
32) of each unit must be unique and
7
8
the unit with the smallest address is
the master unit.
This parameter needs to be set in CAN
No
Yes
networking. Set it to Yes for the first
and last units.
Enable /
CAN
CAN
The networking mode selected on the
network
screen must be consistent with the
actual networking mode.
MAC_CA
The MAC_CAN network and FE
N
N
network are the same teamwork
network
networking mode. The displayed value
or FE
prevails.
network
/
/
The value ranges from 1 to 32.
The value ranges from 1 to the
number of units in the group. Except
/
/
the running units in the group, other
units in the group are used as standby
units.
When the rotation function is enabled,
the running and standby units can
/
/
work alternately. It is recommended
that the function be enabled when the
load is even.
20
Setting Rule