No.
Name
1
Gas pipe
2
Liquid pipe
3
Drainpipe
4
Humidifier
water inlet pipe
a) Weld the refrigerant pipes (gas pipe and liquid pipe).
Avoid damaging the device during welding. Take protective measures around the welding
position, such as spreading wet cloth.
The following describes how to weld refrigerant pipes if pipes are routed from the bottom of
the indoor unit. Welding other refrigerant pipes does not involve removing the bottom plate of
the cabinet and handling holes.
Description
Connection relationship of gas pipe ports:
Without a low temperature component: Indoor unit > Outdoor unit
With a low temperature component: Indoor unit > Low temperature
component > Outdoor unit
Connection relationship of liquid pipe ports:
Without a low temperature component: Indoor unit > Outdoor unit
With a low temperature component: Indoor unit > Low temperature
component > Outdoor unit
Connecting to the drainage system
With a wet film humidifier: connecting to the engineering pipe
Cable hole sealing
Bottom Pipe Routing
Thermal
insulation
foam:
thickness
≥ 9.2 mm
10