5.2
Connecting/Disconnecting Extension Cables
Precautions
• When laying extension cables, maintain the minimum bending radius of 55mm or more.
Failure to do so may cause malfunction due to characteristic deterioration or cable
disconnection.
• Keep the overall cable distance of extension cables within 13.2m.
• Do not install extension cables together with the main circuit (high voltage and large current)
lines.
• When connecting or disconnecting extension cables, do not hold the ferrite cores installed at
both ends of each cable. Hold the connector part of the cable.
Ferrite core
Extension
cable
Holding the ferrite core may cause the cable disconnection inside the connector. Besides, keep
the ferrite core in the correct position. If the ferrite core position is shifted, the characteristic will
change.
Extension cable specifications
The following table lists the extension cables that can be connected to the QA1S6ADP-S1.
Item
Length
Resistance value
Weight
Extension
base unit
Connector
Model
QC05B
QC06B
0.45m
0.6m
0.044
0.051
0.15kg
0.16kg
QC12B
QC30B
1.2m
3.0m
0.082
0.172
0.22kg
0.40kg
QC50B
QC100B
5.0m
10.0m
0.273
0.530
0.60kg
1.11kg
19