DISASSEMBLY PROCEDURE
14. How to remove the water pump
(1) Pull out the module unit assy. (Refer to Procedure 11.)
(2) Remove the module box front. (Refer to Procedure 13-2.)
(3) Remove the module box top and the module box side L
from the module unit assy (13 screws 4x10). (Figure 11-5-
1)
(4) Disconnect the lead wire from the connector of the water
pump. (Photo 14-1)
(5) Disconnect the lead wire of the flow sensor. (Photo 14-2)
(6) Remove the flexible pipe (H-STR) from the water pump (the
G1"nut and the 1" gasket on the flexible pipe side). (Photo
14-2)
(7) Release the THW2 lead wire. (Photo 14-2)
(8) Remove the water pump assy (2 screws 4×10), the
fastener and the O-ring at the P-HEX side). (Photo 14-2
and 14-3)
(9) Remove the pipes of the water pump from the water pump
assy (the fastener and the O-ring at the pump side). (Photo
14-4)
(10) Remove the screws fixing the pump and the pump stay (2
screws 4×10 each at 2 positions). (Photo 14-4)
(11) Remove the upper and lower G1" nuts and the 1" gaskets
at 2 positions from the water pump assy. (Photo 14-4)
Note:
Tightening torque of the G1" nuts: 42 ± 2 N▪m
Tightening torque of the flow sensor: 0.6 ± 0.2 N▪m .
Photo 14-4
Valve
Screws 4×10
G1" Nut
1" Gasket
Valve
*1 When replacing the pump only
● Remove the front panel. (Refer to Procedure 1.)
● Remove the module box front, then close the valves
above and under the pump.
● Remove the G1" nuts and the 1" gaskets on and under
the pump.
*2 When replacing the strainer only
● Remove the front panel. (Refer to Procedure 1.)
● Remove the module box front, then close the valve on
and under the pump.
● Remove the strainer cover on the pump.
Notes:
● Tightening torque of the G1" nut: 42 ± 2 N▪m
● Tightening torque of the strainer cover: 40 ± 2 N▪m
OCH722A
G1" Nut
1" Gasket
Water pump pipe
Fastener and O-ring
Screws 4×10
on the pump side
PHOTOS/ FIGURES
Photo 14-1
Flexible pipe
(Brine out)
Water pump
Connector
Band A
Band B
Photo 14-2
Pipe BH
BPHEX
Fastener and O-ring
on the P-HEX side
Flow sensor
Band D THW2
Photo 14-3
Water pump assy
*1
Valve
G1"
Nuts
Valve
87
Pipe BPUMP
BPHEX
Band C
Flexible pipe
(H-STR)
G1" Nut
1" Gasket
on the flexible
pipe side
Pump stay
Screws 4×10
Strainer
cover
*2