Error code
Title and display conditions
P1/P2/L5/LD
FTC thermistor failure
Note: The thermistors subject to failure can be
checked in "Request code: 567" in "Running
information.
<DHW/Heating/LP/FS/OS>
Error code displayed when thermistor is at open or
short (see table).
Exceptions
Error code will not be displayed for TH2; During
defrost and for 10 minutes after defrost operation.
Error code
Symbol
P1
TH1A/TH1B
P2
TH2
THW1
THW2
THW5A
THW5B
L5
THW6
THW7
THW8
THW9
LD
THWB1
L6
Circulation water freeze protection
<DHW/Heating/LP/FS/OS>
Error code displayed when THW1 detects a temp.
≤ 1ºC for 10 consecutive seconds or THW2
detects a temp. ≤ 3ºC for 10 consecutive seconds.
Exception
Error code will not be displayed if;
FS function is disabled,
For 10 minutes after water circulation pump1 is
switched on.
OCH722A
1.
Connector/terminal wire has become
detached or loose wiring.
2.
Thermistor fault
3.
FTC failure
4.
The thermistor on the wireless remote
controller or the main remote control-
ler may be defective. (when Room
temp. is chosen for the Heating opera-
tion and when Main remote controller
or Room RC 1-8 is chosen for the
Room Sensor setting in the Initial
setting)
5.
Incorrect setting of the DIP switch(es)
Thermistor
Name
Room temperature thermistor
Liquid temperature thermistor
Flow water temperature thermistor
Return water temperature thermistor
Tank upper water temperature thermistor
Tank lower water temperature thermistor
Zone1 flow water temperature thermistor
Zone1 return water temperature thermistor
Zone2 flow water temperature thermistor
Zone2 return water temperature thermistor
Boiler flow water temperature thermistor
1. Insufficient system head
2. Reduced flow in primary water circuit
Due to 1 or more of the following;
Faulty pump, insufficient air purge,
blocked strainer, leak in water circuit
3. Valve operation fault
4. 2-way valve (local supply) actuator
fault
5. 3-way valve actuator fault
6. THW1 has become detached from its
holder.
7. THW1 or THW2 fault
8. FTC board failure
45
Possible Cause
1.
2.
3.
4.
5.
Open detection
−39ºC or below
−39ºC or below
−39ºC or below
−39ºC or below
−39ºC or below
−39ºC or below
−39ºC or below
−39ºC or below
−39ºC or below
−39ºC or below
−40ºC or below
1. Refer to table in "9-6. Checking Component
2. Check circulation pump (See "9-6. Check-
3. Check valves on primary water circuit are
4. Electrically test to determine fault.
5. 1) Electrically test to determine fault.
6. Visually inspect location and reattach as
7. Check resistance of thermistor against table
8. Replace board.
Diagnosis and action
Visually check the terminals and connec-
tions and reattaches appropriate.
Check resistance of thermistor against
table in "9-6. Checking Component Parts'
Function".
Compare FTC detected temperature to
hand held detector.
Replace board.
Replace wireless remote controller or main
remote controller.
Check the DIP switch setting(s).
Short detection
88.5ºC or above
88.5ºC or above
88.5ºC or above
88.5ºC or above
88.5ºC or above
88.5ºC or above
88.5ºC or above
88.5ºC or above
88.5ºC or above
88.5ºC or above
140ºC or above
Parts' Function" to determine if system
pump meets requirements.
If more head required either add a pump of
the same size or replace existing pump with
capacity model.
See "10. DISASSEMBLY PROCEDURE"
for how to replace pump.
ing Component Parts' Function" for how to
check).
Open purge valve to remove trapped air.
Check the strainer for blockages.
Check the primary water circuit for leaks.
Check that the flow amount is within the
recommended range.
installed level.
2) Operate 3-way valve manually using the
main remote controller. (Refer to
<Manual operation> in "8-5. Service
menu".)
3) Replace 3-way valve coil.
4) Replace 3-way valve. (Refer to Procedure
6 in "10. DISASSEMBLY PROCEDURE".)
necessary.
in "9-6. Checking Component Parts'
Function".
Compare FTC detected temperature to
hand held detector.