M E D I U M V O LTA G E P R O D U C T S
7.1.7.
Circuit breaker control card
N.B. Changing the settings by means of dip-switches must be carried out with the control
module de-energised and the capacitor discharged since the selections set and/or modified
are acquired by the control electronics at the moment it is turned on.
Connector for the
storage capacitor/s
and the actuator coils
pos. 1-2:
trip input for
PR12 release
pos. 2-3:
standard opening
input
Jumper only present in the full
option version.It is not normally
short-circuited and energy
consumption during capacitor
charging is 100 W.If it is short-
circuited, energy consumption
during capacitor charging is
reduced to 50 W (the charging time
is obviously doubled)
Connector for:
- closing pushbutton
- opening pushbutton
- luminous "READY" signal
Connector for input signal of
the circuit breaker
open/closed position sensors
Power supply
connector
Presetting of the trip threshold for
the undervoltage function
Rated voltage
Setting
range
35% ... 70%
220-240 V
84 V ... 154 V
3
AC / DC
AC / DC
2
(Normally
1
preset to OFF)
on off
3
100-127 V
45 V ... 70 V
2
AC / DC
AC / DC
1
on off
3
48-60 V
21 V ... 33 V
2
DC
DC
1
on off
3
24-30 V
11 V ... 16 V
2
DC
DC
1
on off
Input connector:
-SO4
(1)
; -SL1; -SO3; -SO2; -SC2
ANSI self-pumping function
5
enabled
on off
ANSI self-pumping function
5
disabled (normally preset)
on off
Automatic opening due to low energy of
the capacitor/s
Disabled (normally preset)
1
on off
1
Enabled (on request)
Enabling for closing with undervoltage function activated
Enabling for closing with undervoltage function activated
3
on off
Enabling for closing only after return of voltage at the undervoltage
3
input (the circuit breaker re-opens after the set delay time)
on off
Selector not used for the VM1 circuit breaker
(the position selected does not matter)
2
on off
Safety opening
(2)
1
Safety opening disabled
on off
Safety opening enabled (normally
1
preset)
on off
Output connector:
DOR; DN; DR; DC2
;
(1)
DO2
; -DC1; DO1
(1)
(
) Full Option version.
1
(
) If enabled, the SO3 input behaves like a hardware input operation even when there is a
2
fault in the microprocessor. If disabled, the –SO3 input behaves like a digital opening
input processed by the microprocessor.
17 17
Presetting of the trip delay
of the undervoltage function
4
Function
3
disabled(normally
preset)
2
on off
4
3
No delay
2
on off
4
3
Delay: 0,5 s
2
on off
4
3
Delay: 1 s
2
on off
4
3
Delay: 2 s
2
on off
4
3
Delay: 3 s
2
on off
4
3
Delay: 4 s
2
on off
4
3
Delay: 5 s
2
on off