6.3. Basic structure of the with-
drawable circuit breaker
The withdrawable truck (4) (fig. 8), either manual
or motorised, consists of a steel sheet structure
with wheels (3), on which the circuit breaker with
the relative auxiliary components, the isolating
contacts (2) for electrical connection with the
switchgear and the multi-pole connector (1) for
connection of the circuit breaker auxiliary circuits
are installed.
After having been racked into the switchgear and
hooked up, the withdrawable circuit breaker can
take up the following positions: racked-out,
isolated for test (with connector inserted) and
racked-in. The racked-in circuit breaker is
automatically earthed by means of the truck
wheels. The magnetic actuator of the circuit
breaker and the relative controls and indicators,
are accessible from the front. Withdrawable
circuit breakers of the same type and
characteristics are interchangeable. However, the
code of the connector prevents incorrect
combinations between the circuit breaker and
switchgear.