Outside Dimensions - Mitsubishi Electric Lossnay LGH-50RVS-E Handbook

Hide thumbs Also See for Lossnay LGH-50RVS-E:
Table of Contents

Advertisement

Model name
Power supply requirement
Power consumption
Transmission cable
Total wiring length
The number of controllable
Lossnay units
Environmental condition
Size
Weight
Color

3. Outside dimensions

LGH-50RVS-E, LGH-80RVS-E, LGH-100RVS-E
By-pass damper plate
RA
(return air)
SA
(supply air)
Air supply fan
Control box
Power supply opening
In the case of fixed ceiling (not grid ceiling),
150 mm or more for drain maintenance
Dimensions
Model
A
LGH-50RVS-E
974
LGH-80RVS-E
1185
LGH-100RVS-E
1185 1224 1179 1279
PZ-62DR-E
Non polarized 2-core cable (0.3 mm
15 Lossnay units maximum (Max. 2 remote controllers installable)
Temperature: 0°C to 40°C, Humidity: 30% to 90% relative humidity (no condensation)
120 x 120 x 19 mm
0.25 kg
Grayish white
Alternative duct position
Inspection
opening
450 x 450
or more
Air filters
Heat exchanger
(Lossnay core)
Backflow stopper
Drain catch basin
Ceiling suspension
Nominal
fixture pitch
diameter
B
C
D
E
946
969
1001
32
997
1179 1051
55
55
12 V DC (Supplied from Lossnay unit)
0.3 W
200 m maximum
Ceiling suspension fixture (4-13 X 20 oval)
Air exhaust fan
EA
(exhaust air outlet)
OA
(outside air intake)
Heat exchanger, Air
filter, High-Efficiency
filter, Fan, Drain pan
maintenance space
High-Efficiency filter (sold separately) position
Maintenance cover for filters (Upper)
Maintenance cover for the other parts (Lower)
Ceiling
Duct connecting
flange
F
G
H
200
192
208
83
250
242
258
82
250
242
258
82
─ 5 ─
PZ-43SMF-E
2
(AWG22) sheathed cable)
120 x 70 x 15 mm
0.10 kg
White
O.D Φ32
Weight with maxi-
Duct pitch
Weight
mum drain water
(kg)
J
K
L
692
127
120
55
683
157
161
63
910
157
161
73
(kg)
67
77
89
Unit (mm)