Battery Calculation Worksheet - GE Alliance AL-2017 Installation Manual

Table of Contents

Advertisement

Battery calculation worksheet

Alliance
Standby
components
current
AL-2017
Aux power
Ext siren
Int siren
Strobe
AL-3017
Aux power
Ext siren
Int siren
Strobe
Comms bus
AL-11XX
120mA
AL-1170
45mA
AL-1191
25mA
AL-1193
25mA
AL-1205
Aux power
Siren
AL-1206
25mA
AL-1210
53mA
AL-1220
53mA
AL-1255/56/65
Aux power
Siren
AL-1801
80mA
AL-1810
100mA
AL-1811
200mA
AL-1830
5mA
AL-1832
15mA
Total current
requirements
Calculations:
1. ______________mA X .001Amp/mA X __________________ hours: ________________ Ah standby Amp-hours
Total standby
current
2. ___________mA X .001Amp/mA X ____________ minutes X .0167 hours/min _____________ Ah alarm Amp-hours
Total alarm
Conversion
current
factor
3. ___________mA X .001Amp/mA X ____________ seconds X .000278 hours/sec ___________ Ah Active Amp-Hours
Total active
current
4. Standby Amp-hours + Alarm Amp-hours + Active Amp-hours = Minimum battery power required
________________ + ______________ + ______________ = _______________Ah
5. Minimum battery power required X Battery capacity derating coefficient = Total standby battery required
___________________________ X ____________________________ = _____________________Ah
AL-2017/AL-3017 Installation Manual
Total standby
Alarm current
current
per device
200mA
300mA
1000mA
1000mA
1000mA
200mA
300mA
1000mA
1000mA
1000mA
1000mA
75mA
250mA
1000mA
275mA
1000mA
1000mA
Conversion
Required number of
factor
hours in standby
Required number of
minutes in alarm
Conversion
Required number of
factor
seconds active
1.15
Total alarm
Active
current
current
80mA
80mA
Conversion
factor
Conversion
factor
Total active
current
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

Alliance al-3017

Table of Contents