GE Alliance AL-2017 Installation Manual page 10

Table of Contents

Advertisement

Figure 10. AL-2017/AL-3017 control panel wiring connections
24 VAC, AL-1290 transformer kit
*
Ademco
AB12M
.
Strobe
Alliance keypad
or other
(BUS)(LAN)
(COMM) Device
Figure 11. Zone (inputs) wiring methods
1 C 2
3 C 4
Note: Method 2, dual zone, is not acceptable
for UL 365, UL 609, and UL 1610 compliance.
AL-2017/AL-3017 Installation Manual
AC
+
BATT
-
+
+
+
-
AUX. POWER
-
-
SW +
SW -
S +
EXT
1K
S -
S +
8 ohm 15 watt
INT
S -
MPI - 35 or EQ
+
STRB
-
NEG
BELL (relay output)
C
POS
+12
OV
COMMS
D +
D -
T
TAMPER
C
5 C 6
7 C 8
Zones (inputs)
Note: Do not short circuit. Use ferrites
on AC input wires.
Note: Refer to Battery Calculation
Worksheet for appropriate battery type.
Note: Total AUX POWER output 300mA,
including +12 on COMMS.
Note: No switched auxiliary output for
the AL-2017.
Note: Alarm output 1 Amp total.
* Siren output must be programmed for
DC output if a bell is connected to these
terminals instead.
A 1k resistor must be installed across the
external siren outputs.
Note: These are dry contacts.
NEG = NC
POS = NO
Note: The first and last device on the
system bus (COMMS) must be terminated.
Method 1
single zone
Zone
input
C
4.7K
NC
Open = Alarm
or Trouble
4.7K
NO
Closed = Alarm
Method 2
dual zone
Zone
input
C
NO
Closed = Tamper
NC
Open = Tamper
or Trouble
4.7K
NC
Open = Alarm
9