GE Kelman Minitrans Installation Manual page 27

Transformer oil dissolved gas and moisture monitor
Hide thumbs Also See for Kelman Minitrans:
Table of Contents

Advertisement

Figure 8-8: Bleed assembly on flange-type oil return valve
If a flange-type valve is to be used to return the oil and the flange is drilled and tapped
to a ¼ in. female NPT fitting, then the drilled hole should be offset to the top of the
internal valve diameter to prevent an air pocket from being trapped behind the flange
(see Figure 8-9).
¼ in. NPT return
Figure 8-9: Flange example
Figure 8-10 depicts the Return Assembly kit.
Check valve
– the arrow
must point
toward the
transformer.
Elbow is
only used if
the ¼ in.
female NPT
fitting face is
vertical; it is
not used if
the ¼ in.
female NPT
fitting face is
horizontal.
Figure 8-10: Return Assembly kit
MA-005 - Minitrans Installation Manual - Rev 4.5
port
Bleed Port
(must be oriented upwards)
Check Valve
Bolt holes
Inside valve diameter
behind the flange
13-Aug-20
Page 27 of 86