Item
EMS
A.4 Cabinet Specifications
Table A-4 Cabinet specifications
Item
Dimensions (H x W x D)
Cabinet weight
Protection level
Installation mode
Issue 03 (2019-11-15)
Specifications
Radiated interference
Harmonic current
Voltage fluctuation and flick
Electrostatic discharge (ESD)
Electrical fast transient (EFT)
Radiated susceptibility (RS)
Conducted susceptibility (CS)
Surge immunity
Voltage dips immunity (DIP)
Specifications
2030 mm x 820 mm x 760 mm (including the 150 mm high base)
TP48200A-HT19C4-1: ≤ 200 kg (excluding rectifiers and batteries)
TBC300A-TCA2: ≤ 56 kg (excluding batteries)
Equipment compartment: IP55
Battery compartment: IP55
TP48200A-HT19C4-1: Can be installed on a floor, rooftop, and
wall, but cannot be stacked or installed along a pole.
TBC300A-TCA2: installed on a floor, installed against a wall
Copyright © Huawei Technologies Co., Ltd.
DC power port: Class A
Class B, EN55022
IEC 61000-3-12
IEC 61000-3-11
Shell ports comply with IEC61000-4-2 (criterion
B).
Contact discharge: 6 kV; air discharge: 8 kV
Signal ports comply with IEC61000-4-2
(criterion R).
Contact discharge: 2 kV
IEC61000-4-4 (criterion B)
AC power port: 2 kV; DC power port: 2 kV
IEC61000-4-3 (criterion A)
10 V/m
IEC6100-4-6 (criterion A)
Power port: 10 V; signal port: 3 V
IEC61000-4-5 (criterion B)
AC power port: differential mode: 2 kV (8/20
us); common mode: 4 kV (8/20 us)
DC power port: differential mode: 2 kV (8/20
us); common mode: 4 kV (8/20 us)
IEC 61000-4-11
A Technical Specifications
79