TP48200A-HT19C4-1 and TBC300A-TCA2 Telecom
Power
User Manual
Item
Rectifier
Site monitoring unit (SMU)
User interface module (UIM)
Sensor
Battery
Maximum output power
Class C environments refer to sea environments or outdoor land environments (with simple shielding
measures) near pollution sources. If a site is near a pollution source, it is at most 3.7 km away from salt
water, such as the sea and salt lakes, 3 km away from heavy pollution sources, such as smelteries, coal
mines, and thermal power plants, 2 km away from medium pollution sources, such as chemical, rubber,
and galvanization industries, and 1 km away from light pollution sources, such as packing houses,
tanneries, and boiler rooms.
Issue 03 (2019-11-15)
TP48200A-HT19C4-1
disconnection (BLVD): two
1-pole 10 A circuit breakers and
four 1-pole 16 A circuit
breakers
Load low voltage disconnection
(LLVD): one 1-pole 100 A
circuit breaker, one 1-pole 63 A
circuit breaker, and four 1-pole
32 A circuit breakers
Battery route: two 1-pole 125 A
circuit breakers
A maximum of four R4850G2s or
R4830G2s can be configured.
One SMU02B
One UIM02C
Mandatory: one battery
temperature sensor, one
ambient temperature sensor in
the equipment compartment,
and one door status sensor
Optional: one smoke sensor,
one ambient temperature and
humidity sensor, and one water
sensor.
The battery compartment with two
layers supports a maximum of two
12 V, 150 Ah battery strings.
12 kW
Copyright © Huawei Technologies Co., Ltd.
TBC300A-TCA2
N/A
N/A
N/A
One door status sensor and one
battery temperature sensor.
Battery compartment of two layers:
two front-access battery strings (12
V/100 Ah) can be configured.
2 Overview