[2-9 Example System with an MA and an ME Remote Controller ]

2-9

Example System with an MA and an ME Remote Controller

2-9-1
System with a Connection of System Controller to Centralized Control
Transmission Line
(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
TB3
M1 M2
TB7
M1 M2
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
TB3
M1 M2
TB7
M1 M2
(2) Cautions
1) Be sure to connect a system controller.
2) ME remote controller and MA remote controller cannot
both be connected to the same group of indoor units.
3) Assign to the indoor units connected to the MA remote
controller addresses that are smaller than those of the in-
door units that are connected to the ME remote control-
ler.
4) No more than 2 ME remote controllers can be connected
to a group of indoor units.
5) No more than 2 MA remote controllers can be connected
to a group of indoor units.
6) Do not connect the terminal blocks (TB5) on the indoor
units that are connected to different outdoor units with
each other.
7) Replace the power jumper connector of the control board
from CN41 to CN40 on only one of the outdoor units.
8) Provide an electrical path to ground for the S terminal on
the terminal block for centralized control on only one of
the outdoor units.
9) A transmission booster must be connected to a system
in which the total number of connected indoor units ex-
ceeds 20.
10) A transmission booster is required in a system to which
HWE14080
L11
Leave the male
Move the male connector
connector on
from CN41 to CN40.
CN41 as it is.
SW5-1 OFF ON
SW5-1 OFF ON
OS2
OS1
OC
53
52
51
TB3
TB3
M1 M2
M1 M2
TB7
TB7
S
M1 M2
S
M1 M2
S
To be left
To be left
unconnected
unconnected
To be connected
L21
Leave the male
Leave the male
connector on
connector on
CN41 as it is.
CN41 as it is.
SW5-1 OFF ON
SW5-1 OFF ON
OS2
OS1
OC
56
55
54
TB3
TB3
M1 M2
M1 M2
TB7
TB7
S
M1 M2
S
M1 M2
S
To be left
To be left
unconnected
unconnected
To be left
unconnected
System controller
A B S
L12
Group
IC
IC
01
02
TB5
TB15
TB5
TB15
M1 M2
S
1 2
M1 M2
S
1 2
A B
MA
L22
Group
Group
IC
IC
03
04
TB5
TB5
TB15
TB15
M1 M2
S
M1 M2
S
1 2
1 2
M1 M2
A B
A B
104
MA
RC
Note1 When only the LM adapter is connected,
leave SW5-1 to OFF (as it is).
Note2 LM adapters require the power supply
capacity of single-phase AC 208/230V.
Note1
more than 16 indoor including one or more indoor units
of the 72 model or above are connected.
Refer to the DATABOOK for further information about
how many booster units are required for a given system.
11) When a power supply unit is connected to the transmis-
sion line for centralized control, leave the power jumper
connector on CN41 as it is (factory setting).
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as 2-7-3
2) Transmission line for centralized control
Same as 2-7-4
3) MA remote controller wiring
Same as 2-7-1
4) M-NET remote controller wiring
Same as 2-7-1
5) Maximum line distance via outdoor unit
2
(1.25 mm
[AWG16] min. )
Same as 2-7-4
- 42 -
Group
IC
06
TB5
TB15
M1 M2
S
1 2
A B
106
RC
IC
05
TB5
TB15
S
1 2
GB