Error Codes [4220, 4225, 4226] Detail Code 131; Error Code [4230] (Tlmu) - Mitsubishi Electric R410A Service Handbook

Hide thumbs Also See for R410A:
Table of Contents

Advertisement

[7-5 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
7-5-17

Error Codes [4220, 4225, 4226] Detail Code 131

1. Error code definition
Low bus voltage at startup (Detail code 131)
2. Error definition and error detection method
When Vdc
160 V is detected just before the inverter operation.
3. Cause, check method and remedy
(1) Inverter main circuit failure
Same as detail code 108 of 4220 error
For inverter-related error codes, refer to the following page(s).
[8-9 Troubleshooting Inverter Problems (TLMU)](page 264)
[8-10 Troubleshooting Inverter Problems (YLMU)](page 276)
7-5-18

Error Code [4230] (TLMU)

1. Error code definition
Heatsink overheat protection
2. Error definition and error detection method
When the heat sink temperature (THHS) remains at or above TOH is detected.
Refer to the relevant pages for the details of model names and the specified values. [7-1-1 Inverter Protection Level Ta-
ble](page 155)
Model
INV24
INV25
3. Cause, check method and remedy
Cause
(1)
Fan board failure
(2)
Outdoor unit fan failure
(3)
Air passage blockage
(4)
THHS failure
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems (TLMU)](page 264)
HWE14080
TOH
100°C [212°F]
90°C [194°F]
Refer to the following page(s).
[8-9-7 Checking the Fan Board Error Detection Circuit at No Load](page 268)
[8-9-8 Checking the Fan Inverter for Damage at No Load](page 269)
[8-9-9 Checking the Fan Inverter for Damage with Load](page 270)
Check the outdoor unit fan operation.
If any problem is found with the fan operation, check the fan motor.
Refer to the following page(s). [8-9-6 Checking the Fan Motor for Ground Fault
and Coil Resistance Problems](page 268)
Check that the heat sink cooling air passage is not blocked
P72, P96, P120, P144 models
1)
Check for proper installation of the INV board IGBT. (Check for proper installa-
tion of the IGBT heatsink.)
2)
Check for proper installation of the INV board IGBT.
If an abnormal value appears, replace the INV board.
P168 model
3)
Check the THHS sensor reading on the LED monitor.
If an abnormal value appears, check the sensor resistance, and replace the
sensor as necessary.