[ II Restrictions ]
1. PUHY
(1) Line branching
Length
Total pipe length
Total pipe length (L) from the outdoor unit to the
farthest indoor unit
Total pipe length from the first branch to the far-
thest indoor unit ( )
Height
Between indoor and
difference
outdoor units
Between indoor units
Outdoor unit
A
L
B
C
D
a
c
First branch
b
Indoor
Indoor
Indoor
Indoor
1
2
3
Operation
Outdoor unit above in-
door unit
Outdoor unit below in-
door unit
A
Note : "Total sum of downstream unit model numbers"
in the table is the sum of the model numbers
of the units after point A in the figure.
e
d
4
Indoor
5
Pipe sections
A+B+C+D
+a+b+c+d+e
A+B+C+D+e
B+C+D+e
H
H'
h
- 54 -
To downstream units
Unit: m [ft]
Allowable length of
pipes
300 [984] or less
150 [492] or less
40 [131] or less
50 [164] or less
40 [131] or less
15 [49] or less