Mitsubishi Electric CITY MULTI PUHY-P108 Service Handbook page 270

Table of Contents

Advertisement

(3) System connected to the system controllers (MELANS)
Error Code
6607
No ACK abnormality
(Contin-
ued)
Error
Error dis-
Detection
source ad-
play
dress
Outdoor
M-NET re-
No ac-
unit
mote con-
knowl-
(OC)
troller (RC)
edgement
system
(ACK) at IC
controller
transmis-
(SC)
sion to OC
MA remote
controller
(MA)
Indoor
M-NET re-
No ac-
unit
mote con-
knowl-
(IC)
troller (RC)
edgement
MA remote
(ACK) at
controller
RC trans-
(MA)
mission to
IC
system
No ac-
controller
knowl-
(SC)
edgement
(ACK) at
SC trans-
mission to
IC
Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the
transmission. (eg. When the data is transmitted six times in a row with 30 seconds
interval, the error is detected on the transmission side.)
Note: The address/attribute appeared on the display on the remote controller
indicates the controller which did not provide the response (ACK).
Cause
method
Same cause as that for system with
one outdoor unit
Same as grouping of units in a sys-
tem with multiple outdoor units
1. Error occurrence on some IC
(1) Same cause as that for system
with one outdoor unit
2. Error occurrence on all IC in the
system with one outdoor unit
(1) Total capacity error (7100)
(2) Capacity code error (7101)
(3) Error in the number of connect-
ed units (7102)
(4) Address setting error (7105)
(5) Disconnection or short circuit of
the transmission line for the out-
door unit on the terminal block
for centralized control line con-
nection (TB7)
(6) Turn off the power source of the
outdoor unit
(7) Malfunction of electrical system
for the outdoor unit
3. Error occurrence on all IC
(1) Same causes as (1) - (7) de-
scribed in 2.
(2) The male power supply connec-
tors on 2 or more outdoor units
are connected to the female
power supply switch connector
(CN40) for the transmission line
for centralized control.
(3) Disconnection or shutdown of
the power source of the power
supply unit for transmission line
(4) System controller (MELANS)
malfunction
- 261 -
[ IX Troubleshooting ]
Check method and remedy
Same remedy as that for system with one
outdoor unit
Same remedy as that for grouping of units
in a system with multiple outdoor units
Same remedy as that for system with
one outdoor unit
1) Check the LED display for troubleshoot-
ing on the outdoor unit.
->If an error is found, check the check
code definition, and correct the error.
->If no error is found, check 2).
2) Check (5) - (7) on the left.
Check voltage of the transmission line for
centralized control.
20V or more : Check (1) and (2) on the
left.
Less than 20V : Check (3) on the left.