Mitsubishi Electric CITY MULTI PUHY-P108 Service Handbook page 334

Table of Contents

Advertisement

-6- LEV
LEV operation
The LEV receives pulse signal from the board and the valve is driven by the stepping motor.
(1) Indoor LEV and BC controller LEV
The valve opening changes according to the number of pulses.
LEV
Blue
4
Brown
6
M
Yellow
2
5
1
3
White Red Orange
Note. The connector numbers on the intermediate connector and the connector on the control board differ. Check the color of the lead wire
to judge the number.
Pulse signal output and valve operation
Output
(phase)
number
1
1
ON
2
ON
3
OFF
3
OFF
LEV valve closing and opening operation
Valve closed
Valve open
A
E
B
80 - 100 pulses
Intermediate connector
4
3
2
1
Output state
2
3
4
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
D
C
Fully open: 1400 pulses
Pulses
Brown
2
Red
5
Blue
1
Orange
3
Yellow
4
White
6
Connector
Indoor unit connector CN60
Control board CNLV1,CNLV2
[Pulse signal output and valve operation]
Output pulses change in the following orders when the
Valve is closed; 1
2
Valve is open;
4
*1. When the LEV opening angle does not change,
all the output phases will be off.
*2. When the output is open phase or remains ON,
the motor cannot run smoothly, and rattles and vibrates.
*When the power is turned on, the valve closing signal of 2200 pulses
will be output from the indoor board to LEV to fix the valve position.
It must be fixed at point A.
When the valve operates smoothly, no sound from LEV or no vibration
occurs, however, when the pulses change from E to A in the chart or
the valve is locked, a big sound occurs.
*Whether a sound is generated or not can be determined by
holding a screwdriver against it, then placing your ear against the handle.
- 325 -
[ IX Troubleshooting ]
Control board
DC 12V
6
5
Drive circuit
4
4
3
3
2
2
1
1
3
4
1
3
2
1
4