Mitsubishi Electric CITY MULTI PUHY-P108 Service Handbook page 214

Table of Contents

Advertisement

Operation
Ambient
Indoor
tempera-
Outdoor
ture
No. of connected
units
Indoor
No. of units in opera-
unit
tion
Operat-
ing condi-
Model
tions
Main pipe
Piping
Branch pipe
Total pipe length
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
(No.1/No.2)
Indoor unit
LEV
opening
SC (LEV1)
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Discharge
(TH11/TH12)
Heat exchanger out-
let (TH5)
Accumu-
lator
Outdoor
unit
Compressor inlet
Temp. of
each sec-
Compressor shell
tion
bottom
SC heat exchanger
outlet (TH7)
Bypass outlet (TH8)
LEV inlet
Indoor
Heat exchanger
unit
outlet
PUHY-P192TGMU-A
DB/
WB
°F
Unit
-
96
48
Ft
-
lbs-
oz
A
V
Hz
388
387
Pulse
psi
Inlet
Outlet
°F
- 205 -
Outdoor unit model
PUHY-P204TGMU-A
80/67
95/-
4
4
36
12
96
16
32
147
Hi
48-11
53.4/48.3
208/230
78/60
325
261
388
204
438/125
183/189
108
59
59
70/63
99/108
77
46
75
55
[ VIII Test Run Mode ]
80/67
95/-
4
4
54
48
18
16
32
147
Hi
61-14
57.7/52.1
208/230
88/60
373
387
362
226
413/123
183/189
104
59
59
66/63
108/108
75
46
73
55