82
Motor connection
Voltage (U
)
2
Frequency
Frequency resolution
Current
Power limit
Field weakening point
Switching frequency
Maximum recommended
motor cable length
Efficiency
Cooling
Method
Free space around the unit
Cooling air flow
Degrees of protection
Prevention of Unexpected Start: AGPS-21 board
Nominal input voltage
Input voltage range
(selected by jumper)
Nominal frequency
Current
Max. external fuse
Input connector X1
User connector 1, 2, 3
Output voltage
Nominal output current
X2 terminal block type
Ambient temperature
Relative humidity
Approvals
Technical data
0 to U
, 3-phase symmetrical, U
1
DTC mode: 0 to 3.2 · f
FWP
U
Nmains
· f
f
=
Nmotor
FWP
U
Nmotor
f
: frequency at field weakening point; U
FWP
U
: rated motor voltage; f
Nmotor
0.01 Hz
See section
IEC ratings.
1.5 · P
, 1.1 · P
or P
hd
N
cont.max
8 to 300 Hz
3 kHz (average). In 690 V units 2 kHz (average).
Type code (EMC equipment)
-
+E202 *, +E210 *
* Motor cable longer than 100 m (328 ft) is allowed but then the EMC Directive requirements may not
be fulfilled.
Approximately 98 % at nominal power level
Internal fan, flow direction from front to top
Refer to ACS800-04/04M/U4 Cabinet Installation [68360323 (English)].
See
IEC ratings.
IP 00 (UL type: open chassis)
115 VAC or 230 VAC
95...132 VAC (X3 on), 185...265 VAC (X4 on, default)
50/60 Hz
0.77 A at 115 V, 0.44 A at 230 V
16 A
2
3 × 2.5 mm
2
600 V, 25 A, 0.5...4 mm
24 V + 0.5 V
1.7 A (50 °C, 122 °F)
JST B3P-VH
0...50 °C (32...122 °F)
30...90 %, no condensation allowed
CE, C-UL US listed
at the field weakening point
max
. Maximum frequency 300 Hz.
: mains (input power) voltage;
Nmains
: rated motor frequency
Nmotor
(whichever value is greatest)
Max. motor cable length
DTC control
300 m (984 ft)
100 m (328 ft)
(20...12 AWG)
Scalar control
300 m (984 ft)
100 m (328 ft)