Dimensions, Weights And Noise; Input Power Connection - ABB ACS800 Hardware Manual

Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

Dimensions, weights and noise

Frame size
mm
R7
1121
R8
1564
H
height
W1 width of the basic unit with PE terminal (bookshelf)
W2 width with the cable connection terminal plates on the left side only (bookshelf)
(R7: width with the cable connection terminal plates on both sides is 579 mm)
(R8: width with the cable connection terminal plates on both sides is 776 mm)
D
depth without fastening brackets
(R7 bookshelf: depth with fastening brackets is 516 mm)
(R8 bookshelf: depth with fastening brackets is 571 mm)
W3 width of the basic unit with PE terminal/busbar (flat)
W4 width with the cable connection terminal plates (flat)
Frame size
R7
H
height without top and bottom exit busbar shrouds
W
width
D
depth
*
weight without top entry and bottom exit shrouds

Input power connection

Voltage (U
)
1
Prospective short-circuit
current (IEC 60439-1)
Frequency
Imbalance
Fundamental power factor
(cos phi
)
1
Busbars on the long side
(bookshelf)
H
W1
W2
mm
mm
334
427
415
562
IP 00, with bottom exit
H
mm
1126
208/220/230/240 VAC 3-phase ± 10 % for 230 VAC units
380/400/415 VAC 3-phase ± 10 % for 400 VAC units
380/400/415/440/460/480/500 VAC 3-phase ± 10 % for 500 VAC units
525/550/575/600/660/690 VAC 3-phase ± 10 % for 690 VAC units
65 kA (Icf)
US and Canada: The drive is suitable for use in a circuit capable of delivering not more
than 65,000 symmetrical amperes (rms) at 600 V maximum.
48 to 63 Hz, maximum rate of change 17 %/s
Max. ± 3 % of nominal phase to phase input voltage
0.98 (at nominal load)
IP 00
Busbars on the short side (flat)
D
H
W3
mm
mm
mm
473
1181
525
568
1596
607
Weight *
W
D
mm
mm
kg
264
471
91
Weight
W4
D
mm
mm
kg
631
259
100
779
403
200
Technical data
81
Noise
dB
71
72

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-04Acs800-04mAcs800-u4