Modbus Data Formats - GE Multilin MM3 Motor Manager 3 Instruction Manual

Hide thumbs Also See for Multilin MM3 Motor Manager 3:
Table of Contents

Advertisement

CHAPTER 8: COMMUNICATIONS
8.4.2
Modbus Data
Formats
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
Table 8–2: Modbus Memory Map (Sheet 28 of 28)
Modicon
Address
dec.
hex
44750
4749
1282
User-definable data
address 0102
44751
4750
1283
User-definable data
address 0103
44752
4751
1284
User-definable data
address 0104
44856
4855
12F7
User-definable data
address 0177
* – Maximum setpoint value and 65535 represent OFF; ** – 1/phase current scale factor × A; *** – 101
represents unlimited;
† – Minimum setpoint value represents OFF; ~ – 0.1 × A when high resolution mode is disabled;
0.01 × A when enabled
F1: Numerical data (unsigned integer)
Format: FFFF
F2: Numerical data (unsigned long integer)
Format: FFFFFFFF
F3: Numerical data (signed long integer)
Format: FFFFFFFF
F4: Hardware version code (enumeration)
1 = A, 2 = B, 3 = C,..., 26 = Z
F5: Cause of stop (enumeration)
Value
Description
0
No stop
1
Process interlock A stop
2
Process interlock B stop
3
Process interlock C stop
4
Process interlock D stop
5
External stop
6
ESD stop
7
Process interlock E stop
8
Process interlock F stop
9
Process interlock G stop
F6: Command mode (enumeration)
Value
Description
0
Manual
1
Auto
2
Manual inhibit
3
Manual and auto
4
Hard-wire auto
F7: Drive status (enumeration)
Value
Description
0
Unavailable
Description
Range
0000 to
12FF
0000 to
12FF
0000 to
12FF
0000 to
12FF
Value
10
11
12
13
14
15
16
17
18
MODBUS MEMORY MAP
Step
Units
Format
Default
1
---
F1
1
---
F1
1
---
F1
1
---
F1
Description
Process interlock H stop
Process interlock I stop
Process interlock J stop
Faceplate stop
Process stop
Serial stop
Two-wire stop
Stop A interlock stop
Stop B interlock stop
0
0
0
0
8–43

Advertisement

Table of Contents
loading

Table of Contents