CHAPTER 8: COMMUNICATIONS
8.4.2
Modbus Data
Formats
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
Table 8–2: Modbus Memory Map (Sheet 28 of 28)
Modicon
Address
dec.
hex
44750
4749
1282
User-definable data
address 0102
44751
4750
1283
User-definable data
address 0103
44752
4751
1284
User-definable data
address 0104
↓
↓
↓
↓
44856
4855
12F7
User-definable data
address 0177
* – Maximum setpoint value and 65535 represent OFF; ** – 1/phase current scale factor × A; *** – 101
represents unlimited;
† – Minimum setpoint value represents OFF; ~ – 0.1 × A when high resolution mode is disabled;
0.01 × A when enabled
F1: Numerical data (unsigned integer)
Format: FFFF
F2: Numerical data (unsigned long integer)
Format: FFFFFFFF
F3: Numerical data (signed long integer)
Format: FFFFFFFF
F4: Hardware version code (enumeration)
1 = A, 2 = B, 3 = C,..., 26 = Z
F5: Cause of stop (enumeration)
Value
Description
0
No stop
1
Process interlock A stop
2
Process interlock B stop
3
Process interlock C stop
4
Process interlock D stop
5
External stop
6
ESD stop
7
Process interlock E stop
8
Process interlock F stop
9
Process interlock G stop
F6: Command mode (enumeration)
Value
Description
0
Manual
1
Auto
2
Manual inhibit
3
Manual and auto
4
Hard-wire auto
F7: Drive status (enumeration)
Value
Description
0
Unavailable
Description
Range
0000 to
12FF
0000 to
12FF
0000 to
12FF
↓
0000 to
12FF
Value
10
11
12
13
14
15
16
17
18
MODBUS MEMORY MAP
Step
Units
Format
Default
1
---
F1
1
---
F1
1
---
F1
↓
↓
↓
1
---
F1
Description
Process interlock H stop
Process interlock I stop
Process interlock J stop
Faceplate stop
Process stop
Serial stop
Two-wire stop
Stop A interlock stop
Stop B interlock stop
0
0
0
↓
0
8–43