S3 Process; Programmable Inputs - GE Multilin MM3 Motor Manager 3 Instruction Manual

Hide thumbs Also See for Multilin MM3 Motor Manager 3:
Table of Contents

Advertisement

S3 PROCESS

5.4.1
Programmable
Inputs
] PROGRAMMABLE
] INPUTS
NOTE
5–22
5.4
S3 Process
PATH: S3 PROCESS

PROGRAMMABLE INPUTS

The first five setpoints are repeated for all ten interlock outputs.
The programmable input settings are programmed as follows:
INTERLOCK INPUT 1(10): Interlock input functions are active when the applicable
switch input is closed and energized. Once a function is assigned to an interlock input,
it cannot be assigned to any other interlock input. The range options are as follows:
• "NOT USED": Select this value if the interlock switch input is not used.
• "PROCESS INTERLOCK A to J": The process interlock functions provide time-
dependent trip/alarm/stop features based on a switch input. This function is used
INTERLOCK INPUT 1:
NOT USED
STARTUP OVERRIDE
DELAY:
0 s
RUNNING OVERRIDE
DELAY:
0 s
OPERATION:
INTERLOCK STOP
INSTANTANEOUS ALARM:
DISABLE
INTERLOCK INPUT 2:
NOT USED
INSTANTANEOUS ALARM:
DISABLE
IL1 SWITCH TYPE:
N.O.
LOCAL ISOLATOR:
DISABLE
AUTO PERMISSIVE
INDICATION: MANUAL
AUTO MODE:
SERIAL
SERIAL PERMISSIVE:
DISABLE
START BLOCK ALARM:
DISABLE
DISABLE COMMAND MODE
CHANGE WHEN RUNNING
SWITCH INPUT MONITOR
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
Range:
see below
Range:
0 to 3600 s or OFF in steps of 1
Range:
0 to 3600 s or OFF in steps of 1
Range:
INTERLOCK STOP, LATCHED
TRIP
Range:
ENABLE, DISABLE
Range:
see below
Range:
ENABLE, DISABLE
Range:
N.O., N.C.
Range:
ENABLE, DISABLE
Range:
MANUAL, AUTO
Range:
SERIAL, HARD-WIRED
Range:
ENABLE, DISABLE
Range:
ENABLE, DISABLE
Range:
ENABLE, DISABLE
Range:
ENABLE, DISABLE