Common bus regeneration mode with harmonic suppression enabled
(Pr.416 = "1")
When connecting the multifunction regeneration converter (FR-XC) to suppress power harmonics, perform wiring securely as
follows. Incorrect connection will damage the multifunction regeneration converter and the inverter.
Turn ON switch 1 (connection mode setting switch) in the function selection switch assembly (SW2). If the switch setting does
not match the actual wiring, the connection mode fault "E.T" occurs.
After making sure that the wiring is correct and secure, set the rated motor voltage in Pr.19 Base frequency voltage (under
V/F control) or Pr.83 Rated motor voltage (under other than V/F control) and "2 or 102" in Pr.30 Regenerative function
selection. (Refer to the Instruction Manual (Detailed) of the FR-A800 inverter.)
MC
MCCB
∗7
Fuse
R/L1
∗7
Fuse
S/L2
Power
supply
∗7
Fuse
T/L3
FR-XC
FR-XCB
∗4∗8
R2/L12
R2/L12
S2/L22
S2/L22
T2/L32
T2/L32
LOH1
LOH
LOH2
RES
SOF
SD
SD
PC
RYB
FAN1
FAN
RSO
∗4∗5
R/L1
S/L2
T/L3
Connection of stand-alone option units
Junction terminal
P/+
Fuse
N/-
Fuse
SE
Junction terminal
Fuse
Fuse
Junction terminal
Fuse
Fuse
INSTALLATION AND WIRING
Inverter
∗1
U
R/L1
V
S/L2
IM
M
W
T/L3
R1/L11
S1/L21
∗2∗3
P/+
P1
N/-
∗6
X10(MRS)
RES
SD
Inverter
∗1
U
R/L1
V
S/L2
IM
M
W
T/L3
R1/L11
S1/L21
∗2∗3
P/+
P1
N/-
∗6
X10(MRS)
RES
SD
Inverter
∗1
U
R/L1
V
S/L2
IM
M
W
T/L3
R1/L11
S1/L21
∗2∗3
P/+
P1
N/-
∗6
X10(MRS)
RES
SD
69