3.6.3
Connection of MCP 535x and MCP 545x manual call points
1
2
3
SHLD
L2
GND
MCP 535X
Fig. 19 MCP 535x connection
3.6.4
Connection of BX-AIM advanced input module
The BX-AIM advanced input module can be used as monitored input for polling potential-free contacts or as detection zone
for connecting collective detectors. Among other things, it can be used to connect intrinsically safe detectors (Ex-i) with inter-
mediate switching of a
Zener
More information about the BX-AIM can be found in the data sheet T 131 436.
Collective detector and monitored input
MMD130 Ex-i in Ex area
Ex-area
19k1
Last detector
4
5
6
7
8
SHLD
barrier. An output for a repeat signal is also available.
Fig. 21 BX-AIM, collective detector and monitored input
Max. 4 USB 501-7 Ex-i detector bases
Fig. 22 BX-AIM, MMD130 Ex-i in Ex area
Mounting and Installation, Technical Description, T 811 065 en
L1
GND
GND
L2
SHLD
Repeat signal
BX-AIM
X1
1
P-
SHLD
SHLD
P+
L
GND
C
GND
L Ex
Interfaces & connections
MCP 545X
MCP 545N
Fig. 20 MCP 545x connection
X2
L2
L1
1
Safety barrier
Z787F
1
+
X1
-
4
1
P-
-
5
P+
L
+
-
C
8
L Ex
+
Local earthing safety barrier,
additional equipotential bonding 10 mm to FACP earthing
SHLD
L1
GND
BX-AIM
X2
SHLD
SHLD
L2
GND
GND
L1
1
2
25 / 41