SecuriLine eXtended
10.3.3
Connection of MCP 535x and MCP 545x manual call points
1
2
3
SHLD
L2
GND
MCP 535X
Fig. 126 MCP 535x connection
10.3.4
Connection of BX-AIM advanced input module
The BX-AIM advanced input module can be used as monitored input for polling potential-free contacts or as detection zone
for connecting collective detectors. Among other things, it can be used to connect intrinsically safe detectors (Ex-i) with in-
termediate switching of a
Further information about the BX-AIM can be found in the data sheet T 811 100.
Collective detector and monitored input
Indicator
560 R
19k1
Fig. 128 BX-AIM, collective detector and monitored in-
MMD130 Ex-i in Ex area
Ex-area
19k1
Last detector
102 / 128
Mounting and installation, Technical Description, T 811 086 en e
4
5
6
7
8
Zener
barrier. An output for a repeat signal is also available.
BX-AIM
X1
X2
P-
1
SHLD
SHLD
P+
L2
L
GND
C
GND
L Ex
L1
1
put
Max. 4 USB 501-7 Ex-i detector bases
Fig. 130 BX-AIM, MMD130 Ex-i in Ex area
SHLD
L1
GND
GND
L2
SHLD
Extinguishing input in accordance with VdS
Extinguisching
control panel
3k3
Fig. 129 BX-AIM, extinguishing input compliant with VdS
MCP 545X
MCP 545N
Fig. 127 MCP 545x connection
X1
680 R
P-
1
P+
L
C
L Ex
Safety barrier
Z787F
1
X1
+
1
P-
-
4
P+
-
L
5
-
C
+
+
8
Local earthing safety barrier,
additional equipotential bonding 10 mm to FACP earthing
SHLD
L1
GND
BX-AIM
X2
SHLD
SHLD
L2
GND
GND
L1
1
BX-AIM
X2
SHLD
SHLD
L2
GND
GND
L Ex
L1
1
2